Deif SGC 420 User Manual page 24

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

Cyclic Mode
Parameter
Cyclic Mode
Genset Off Time
Genset On Time
Auto Exercise – Event 1
Parameter
Auto Exercise
Event Occurrence
Event Day
Start Time
Duration
Load Transfer
Auto Exercise – Event 2
Parameter
Auto Exercise
Event Occurrence
Event Day
Start Time
Duration
Load Transfer
User manual 4189341341B EN
Range
Enable
Disable
1 to 720 minutes
1 to 720 minutes
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
00:00 to 23:59 hour
00 hr 01 min. to 99 hr
59 min.
Enable
Disable
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
00:00 to 23:59 hours
00 hr 01 min. to 99 hr
59 min.
Enable
Disable
Default
Not enabled
15 minutes
15 minutes
Default
Not enabled
Daily
Runs every day
10:00 hour
10 hours, 10 minutes
Not enabled
Default
Not enabled
Daily
Runs every day
09:59 hours
10 hours, 10 minutes
Not enabled
Description
If you enable this parameter, the controller
operates in cyclic mode.
Select the time duration for when the genset is
not operating.
Select the time duration for when the genset is
operating.
Description
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Configure how often the sequences occur.
Configure the start date for the sequences.
Configure the start time for the sequences.
Configure for how long the genset operates
during the scheduled sequences.
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
Description
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Configure how often the sequences occur.
Configure the start date for the sequences.
Configure the start time for the sequences.
Configure for how long the genset operates
during the scheduled sequences.
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
Page 24 of 89