Parameter
(FLS) Warning
Threshold
(FLS) Fuel Tank
Capacity
(FLS) Fuel Theft
Warning
(FLS) Fuel Theft Alarm
Threshold
(FLS) Circuit Fault
Action
(FLS) Fuel Sensor
Reference
(FLS) Fuel Level
Sensor Calibration
Table
Analogue Input 3
Parameter
Use Input As
(Digital) Source
Name
(Digital) Polarity
(Digital) Action
(Digital) Activation
(Digital) Activation
Delay
(ETS) Circuit Fault
Action
User manual 4189341341B EN
Range
2 to 80 %
2 to 1000 litre
Enable
Disable
1 to 100 % per hour
None
Notification
Warning
Electrical Trip
Shutdown
Battery Negative
Engine Body
Resistance: 0 to 5000
Ω
Fuel level: 0 to 100 %
Range
Not used
Digital Input L
Engine Coolant
Temperature Sensor
See Digital input
source selection in
this document
Auxiliary Input L
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
None
Notification
Warning
Electrical Trip
Default
50 %
100 litre
Enabled
50 %
None
Engine Body
-
Default
Not used
Not used
-
Close to Activate
None
From Monitoring On
1 s
None
Description
The controller shows a notification when the
fuel level is less than this set point.
Configure the fuel tank capacity.
If this parameter is enabled, the controller
activates an alarm when the fuel level is less
than the set point for the fuel theft alarm.
If the fuel consumption per hour is more than
this set point, the controller activates an alarm.
The percentage is of the nominal fuel
consumption.
Configure the action for when there is an open
circuit failure.
Select the reference point for the fuel sensor.
Configure the resistance and pressure values
for the 10 measurement points in the calibration
table.
Description
Select what to use the input as.
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Configure from when the digital input is
monitored.
If the input is active when the timer expires, the
controller actives the action for the digital input.
Configure the action for an open circuit failure.
Page 27 of 89