Generator - Deif SGC 420 User Manual

Single genset controller
Hide thumbs Also See for SGC 420:
Table of Contents

Advertisement

General
Parameter
Power Save Mode
Delay
Screen Changeover
Time
Deep Sleep Mode
Delay
Sounder Alarm Time
Test Mode Timer
Auto Exit Config Mode
Inlet shutoff Valve Pull
Signal
Gen Breaker Pulse
Timer
Mains Breaker Pulse
Timer
Breaker Feedback
Timer
Breaker Close Delay
3.5.6

Generator

Alternator configuration
Parameter
Alternator Present
Number of Poles
AC system
Min Healthy Voltage
Min Healthy Frequency 10 to 100 Hz
Phase Reversal
Detection
Phase Reversal Action
User manual 4189341341B EN
Range
5 to 1800 s
1 to 1800 s
5 to 1800 s
1 to 300 s
1 to 720 minutes
10 to 1800 s
0 to 2 s
0 to 5 s
0 to 5 s
1 to 10 s
1 to 10 s
Range
Yes
No
2, 4, 6, or 8
Single phase (L1-N)
3-phase (L1-L2-L3-N)
Split-phase (L1-N-L2)
Split-phase (L1-N-L3)
2-phase (L1-L2-N)
2-phase (L1-L3-N)
3-phase (L1-L2-L3)
10 to 100 V phase-
neutral
Enable
Disable
None
Notification
Warning
Default
30 s
3 s
10 s
5 s
3 minutes
10 s
0.1 s
0.5 s
0.5 s
2 s
2 s
Default
No
4
3-phase
40 V
40 Hz
Enabled
None
Description
If the controller is not in use, the backlight turns
off when the timer expires.
The display page changes when the timer
expires.
If the controller is not in use, the controller goes
into deep sleep mode when the timer expires.
The alarm is activated when the alarm output is
activated. The alarm stops when the timer
expires.
Engine run time during the test period.
If the controller is not in use, the controller
automatically exits the configuration mode
when the timer expires.
The output for the pull signal for the inlet
shutoff valve is active for this time duration.
The time duration for the genset breaker pulse.
The time duration for the mains breaker pulse.
The timer for breaker feedback.
Configure the time to charge the generator
breaker spring before the breaker closes.
Description
No: All generator parameters are not enabled.
Yes: All generator parameters are enabled.
The pole number in the alternator.
Select the AC system for the generator.
When the voltage has reached the set point,
the genset starts to warm up.
When the frequency has reached the set point,
the genset starts to warm up.
If this parameter is enabled, a phase reversal is
detected if the phase sequence is not L1-L2-L3.
Configure the action for phase reversal
detection.
Page 34 of 89