Parameter
(S1) Calibration Table
(STS) High Temp
Threshold
(STS) Shelter Temp
Hysteresis
(STS) Shelt Temp
Monitoring Delay
(STS) Shelt Temp Run
Duration
(STS) Calibration Table
(Resistive)
S2 Sensor
Parameter
Use Input As
(Digital) Source
Name
(Digital) Polarity
(Digital) Action
(Digital) Activation
(Digital) Activation
Delay
(S2) Shutdown
(S2) Shutdown
Threshold
User manual 4189341341B EN
Range
Resistance: 0 to 5000
Ω
Value: 0 to 1000
25 to 300 °C
1 to 100 °C
5 to 300 s
1 to 720 min.
Resistance: 0 to 5000
Ω
Temperature: -25 to
300 °C
Range
Not used
Digital Input N
S2 Sensor
See Digital input
source selection in
this document
Auxiliary Input N
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
Enable
Disable
0.0 to 1000.0
Default
-
60 °C
5 °C
10 s
60 min.
-
Default
Not used
Not used
-
Close to Activate
None
From Monitoring On
1 s
Not enabled
2
Description
Configure the resistance values for 10
measurement points in the calibration table.
If the battery temperature is more than this set
point, the controller starts the genset.
If the shelter temperature hysteresis is less
than this set point when the genset operates,
the controller stops the genset. This is only if
the battery voltage is OK and there is a mains
failure.
If the shelter temperature is more than the set
point for high shelter temperature when the
timer expires, the controller activates an alarm.
In AUTO mode, the genset operates for this
time duration when the shelter temperature is
more than the high temperature set point
(SHELT TEMP THRESH).
Configure the resistance and temperature
values for 10 measurement points in the
calibration table.
Description
Select what to use the input as.
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Configure from when the digital input is
monitored.
If the input is active when the timer expires, the
controller actives the action for the digital input.
If this parameter is enabled, the controller shuts
down the engine when the monitored value is
less than or more than the shutdown set point.
If the monitored value is more than or less than
this set point, the controller shuts down the
engine.