Night Mode
Parameter
Night Mode
Night Mode Start Time 00:00 to 23:59 hour
Night Mode Off
Duration
3.5.2

Digital inputs

Digital Input #
Parameter
Source
Name
Polarity
Action
Activation
Activation Delay
3.5.3

Analogue inputs

Analogue Input 1
Parameter
Use Input As
(Digital) Source
Name
(Digital) Polarity
(Digital) Action
User manual 4189341341B EN
Range
Enable
Disable
1 to 1440 minutes
Range
See Digital input
source selection in
this document
Auxiliary Input #
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
0 to 60 s
Range
Not used
Digital Input J
Lube Oil Pressure
See Digital input
source selection in
this document
Auxiliary Input J
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Default
Not enabled
09:00 hour
10 minutes
Default
-
-
Close to Activate
None
From Monitoring On
1 s
Default
Not used
Not used
-
Close to Activate
None
Description
In this mode, the controller is off until the night
mode timer expires. You can configure when
night mode is active.
The night mode is activated, when the start
timer starts.
Night mode is active until the Night Mode Off
timer expires.
Description
Select an input source from the list.
You can configure the name of the input.
You can select how to activate the input. It can
be open or close with reference to ground.
You can configure what action occurs when the
digital input is activated.
You can configure when the controller starts to
monitor the digital input.
When the timer expires, the configured action
occurs.
Description
Select the input.
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Page 25 of 89