Parameter
(S2) Warning
(S2) Warning
Threshold
(S2) Threshold Type
(S2) Circuit Fault
Action
(S2) Calibration Table
S3 Sensor
Parameter
Use Input As
(Digital) Source
Name
(Digital) Polarity
(Digital) Action
(Digital) Activation
(Digital) Activation
Delay
(4-20 mA) Shutdown
(4-20 mA) Shutdown
Threshold
(4-20 mA) Warning
User manual 4189341341B EN
Range
Enable
Disable
0.0 to 1000.0
Greater Than
Threshold
Less Than Threshold
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 0 to 5000
Ω
Value: 0 to 1000
Range
Not used
Digital Input O
4 to 20 mA Sensor
0 to 5 V Sensor
See Digital input
source selection in
this document
Auxiliary Input O
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
Enable
Disable
0.0 to 1000.0
Enable
Disable
Default
Not enabled
3
Less Than Threshold
None
-
Default
Not used
Not used
-
Close to Activate
None
From Monitoring On
1 s
Not enabled
2
Not enabled
Description
The controller activates a warming alarm when
this parameter is enabled.
If the monitored value is more than or less than
this set point, the controller activates a warning
alarm.
Configure if the controller activates a shutdown
and/or a warning when the monitored value is
less than or more than the set points.
Configure the action for when there is an open
circuit failure.
Configure the resistance values for 10
measurement points in the calibration table.
Description
Select what to use the input as.
Select the source from the list.
You can configure the name of the input.
Select the polarity for the input.
Select the action when the input is activated.
Configure from when the digital input is
monitored.
If the input is active when the timer expires, the
controller actives the action for the digital input.
If this parameter is enabled, the controller shuts
down the engine when the monitored value is
less than or more than the shutdown set point.
If the monitored value is more than or less than
this set point, the controller shuts down the
engine.
The controller activates a warming alarm when
this parameter is enabled.
Page 30 of 89