• Use the Up
and Down
• oc##: Shows how many times a specific alarm has occurred.
• CLRALL: Push ENTER to clear the entire alarm log list. For safety reasons, this requires the master password.
NOTE
If the controller has no translation text for an SPN diagnostic number, Text N/A is shown. For information about
particular SPN numbers, see the engine manufacturer's documentation. Alternatively, see SAE J1939-71 for a
general description.
Controls to the ECU
Command
Speed
Start/stop
Pre-heat
Measurements from the ECU
Command
Lube oil pressure
Coolant temperature
Engine speed
Running hours
Battery voltage
TSC1 SA Torque Speed Control
Torque Speed Control 1 (TSC1) is the speed control signal from the SGC to the ECU. For known protocols, the SGC uses the
expected source address when TSC1 SA is -1 (default value). You can configure the controller for a specific source address
(the range is 0 to 255). Ask the engine manufacturer to verify the TSC1 source address.
User manual 4189341341B EN
buttons to go through the alarm list.
Description
The controller writes the configured engine speed to the ECU.
The controller writes the start/stop commands to the ECU.
The pre-heat function is activated when the controller writes this command to the ECU.
The pre-heat output does not need to be configured.
Description
The controller can read and monitor the lube oil pressure from the ECU.
The controller can read and monitor the coolant temperature from the ECU.
The controller can read and monitor the engine speed form the ECU.
The controller can read and monitor the running hours from the ECU.
The controller can read and monitor the battery voltage from the ECU.