Generator - Deif SGC 121 User Manual

Single genset controller
Hide thumbs Also See for SGC 121:
Table of Contents

Advertisement

Parameter
Engine Cooling Time
(ENG COOL TIME)
Stop Action Time
(STOP ACTION TIME)
Additional Stopping
Time
(ADDN STOPPING
TIME)
Load Transfer Delay
(LOAD TRANSFER
DELAY)
Power Save Mode
Delay
(PWR SAVE MODE
DELAY)
Screen Changeover
Time
(SCRN CHNGOVER
TIME)
Deep Sleep Mode
Delay
(DEEP SLP MODE
DELAY)
Sounder Alarm Time
(SOUNDER ALARM
TIMER)
Auto Exit Config Mode
(AUTO EXIT CNFG
MODE)
Inlet shutoff Valve Pull
Signal
Gen Breaker Pulse
Timer
Mains Breaker Pulse
Timer
Breaker Feedback
Timer
Breaker Close Delay
3.5.6

Generator

Alternator configuration (ALT CONFIG)
Parameter
Alternator Present
(ALT PRESENT)
Number of Poles
(NUMBER OF POLES)
AC system
(ALT AC SYSTEM)
User manual 4189341354A EN
Range
0 to 300 s
10 to 120 s
0 to 120 s
0 to 60 s
5 to 1800 s
1 to 1800 s
5 to 1800 s
1 to 300 s
10 to 1800 s
0 to 2 s
0 to 5 s
0 to 5 s
1 to 10 s
1 to 10 s
Range
Yes
No
2/4/6/8
1 phase
3 phase
Default
5 s
30 s
10 s
1 s
30 s
3 s
10 s
5 s
10 s
0.1 s
0.5 s
0.5 s
2 s
2 s
Default
No
4
3-phase
Description
When the engine cooling timer expires, the
engine stops.
The time duration for the stop action sequence.
Additional time added to the engine stop
sequence.
The time it takes to transfer the load to the
mains or genset.
If the controller is not in use, then the backlight
turns off when the timer expires.
The display page changes when the timer
expires.
If the controller is not in use, the controller goes
into deep sleep mode when the timer expires.
The alarm is activated when the alarm output is
activated. The alarm stops when the timer
expires.
If the controller is not in use, the controller
automatically exits the configuration mode
when the timer expires.
The output for the pull signal for the inlet
shutoff valve is active for this time duration.
The time duration for the genset breaker pulse.
The time duration for the mains breaker pulse.
The timer for breaker feedback.
Configure the time to charge the generator
breaker spring before the breaker closes.
Description
No: All generator parameters are not enabled.
Yes: All generator parameters are enabled.
The pole number in the alternator.
Select if it is a single phase genset or a 3-phase
genset.
Page 27 of 72