General (GENERAL TIMER)
Parameter
Power Save Mode
Delay
(PWR SAVE MODE
DELAY)
Screen Changeover
Time
(SCRN CHNGOVER
TIME)
Deep Sleep Mode
Delay
(DEEP SLP MODE
DELAY)
Sounder Alarm Time
(SOUNDER ALARM
TIMER)
Test Mode Timer
(TEST MODE TIMER)
Auto Exit Config Mode
(AUTO EXIT CNFG
MODE)
Inlet shutoff Valve Pull
Signal
Gen Breaker Pulse
Timer
Mains Breaker Pulse
Timer
Breaker Feedback
Timer
Breaker Close Delay
3.5.6

Generator

Alternator configuration (ALT CONFIG)
Parameter
Alternator Present
(ALT PRESENT)
Number of Poles
(NUMBER OF POLES)
AC system
(ALT AC SYSTEM)
Min Healthy Voltage
(MIN HEALTHY VOLT)
Min Healthy Frequency
(MIN HEALTHY FREQ)
Phase Reversal
Detection
(PHASE REVERSAL
DETECT)
User manual 4189341355A EN
Range
5 to 1800 s
1 to 1800 s
5 to 1800 s
1 to 300 s
1 to 720 minutes
10 to 1800 s
0 to 2 s
0 to 5 s
0 to 5 s
1 to 10 s
1 to 10 s
Range
Yes
No
2, 4, 6, or 8
Single phase
3-phase
10 to 100 V phase-
neutral
10 to 100 Hz
Enable
Disable
Default
30 s
3 s
10 s
5 s
3 minutes
10 s
0.1 s
0.5 s
0.5 s
2 s
2 s
Default
No
4
3-phase
40 V
40 Hz
Enabled
Description
If the controller is not in use, the backlight turns
off when the timer expires.
The display page changes when the timer
expires.
If the controller is not in use, the controller goes
into deep sleep mode when the timer expires.
The alarm is activated when the alarm output is
activated. The alarm stops when the timer
expires.
Engine run time during the test period.
If the controller is not in use, the controller
automatically exits the configuration mode
when the timer expires.
The output for the pull signal for the inlet
shutoff valve is active for this time duration.
The time duration for the genset breaker pulse.
The time duration for the mains breaker pulse.
The timer for breaker feedback.
Configure the time to charge the generator
breaker spring before the breaker closes.
Description
No: All generator parameters are not enabled.
Yes: All generator parameters are enabled.
The pole number in the alternator.
Select if it is a single phase genset or a 3-phase
genset.
When the voltage has reached the set point,
the genset starts to warm up.
When the frequency has reached the set point,
the genset starts to warm up.
If this parameter is enabled, a phase reversal is
detected if the phase sequence is not L1-L2-L3.
Page 35 of 92