Stop Action Time
(STOP ACTION TIME)
Additional Stopping Time
(ADDN STOPPING TIME)
Load Transfer Delay
(LOAD TRANSFER DELAY)
Power Save Mode Delay
(PWR SAVE MODE DELAY)
Screen Changeover Time
(SCRN CHNGOVER TIME)
Deep Sleep Mode Delay
(DEEP SLP MODE DELAY)
Sounder Alarm Time
(SOUNDER ALARM TIMER)
Auto Exit Config Mode
(AUTO EXIT CNFG MODE)

6.2.7 Generator

Table 6.10
Alternator configuration (ALT CONFIG)
Level 2
Alternator Present
(ALT PRESENT)
Number of Poles
(NUMBER OF POLES)
AC system
(ALT AC SYSTEM)
Min Healthy Voltage
(MIN HEALTHY VOLT)
Min Healthy Frequency
(MIN HEALTHY FREQ)
Phase Reversal Detection
(PHASE REVERSAL DETECT)
Phase Reversal Action
(PHASE REVERSAL ACTION)
Auto Load Transfer
(AUTO LOAD TRANSFER)
Table 6.11
Voltage Monitoring (VOLT MONITOR)
Level 2
Under-voltage Shutdown
(UNDER VOLT SHUTDOWN)
Under-voltage Shutdown Threshold
(UV SHUTDOWN THRESH)
USER MANUAL 4189341228A UK
Range
10 to 120 s
0 to 120 s
0 to 60 s
5 to 1800 s
1 to 1800 s
5 to 1800 s
1 to 300 s
10 to 1800 s
Range
Yes
No
2/4/6/8
1 phase
3 phase
50 to 350 V phase-neutral
10 to 75 Hz
Enable
Disable
None
Notification
Warning
Electrical Trip
Shutdown
Enable
Disable
Range
Enable
Disable
50 to 295 V phase-neutral