3.10 Magnetic pick-up (MPU) input

Category
Controller terminal
Measurement type
Frequency range
Input voltage range
The Magnetic pick-up (MPU) is an inductive sensor fitted on the engine flywheel for the engine speed sensing. The output of the
MPU is a sine-wave signal.

3.11 Digital outputs

Category
Controller terminals
Number of outputs
Type
Maximum current rating
Software configurable options
NOTE
Do not connect the starter motor relay and the stop solenoid directly to the controller's output terminals.
Genset and mains contactor latching relays should be compiled against 4 kVA surge as per IEC-61000-4-5 standard.

3.12 Rotary actuator outputs (SGC 121 only)

Category
Controller terminal
Type
Max. current
The actuator outputs are used only for the Rotary actuator, if installed. The Rotary actuator is a 4-wire actuator that is used for
creating an electronic governing application in case of a mechanical fuel system engine. In diesel engines, the Rotary actuator's
shaft output gets mechanically connected to the stop lever or the throttle lever of an in-line or rotary fuel injection pump. In case of
petrol or natural gas engines, the Rotary actuator's shaft output gets connected to the throttle/charge control valve.
It is recommended to follow the connection details of the Rotary actuator connector and SGC 121.
USER MANUAL 4189341226A UK
Specifications
42
Single ended
10 to 10 kHz
200 mV to 45 V AC RMS
Specifications
3, 4, 5, 6, 8, 9
6
DC outputs
Max. per output: 500 mA
Total max.: 1 A
Start relay, Fuel relay and many more (see Controller overview,
Configurable parameters for more details).
Specifications
17, 18. 19 and 20
Stepper motor drive
1 A
Page 13 of 72