3.4.2 Digital outputs

Do not connect the starter motor relay and the stop solenoid directly to the output terminals on the controller.
The current rating is 5 A for terminals 3 and 4, and 1 A for terminals 5, 6, 7, 8, and 9.
NOTE
Protect the genset and mains breaker relays against 4 kVA surges as described in IEC-61000-4-5.

3.4.3 Power supply and start

Do not connect the starter motor relay and the stop solenoid directly to the output terminals on the controller.
NOTE
Remember to mount the freewheeling diodes.
User manual 4189341360A EN
Page 21 of 99