3.4.2 Digital outputs
Do not connect the starter motor relay and the stop solenoid directly to the output terminals on the controller.
The current rating is 5 A for terminals 3 and 4, and 1 A for terminals 5, 6, 7, 8, and 9.
NOTE
Protect the genset and mains breaker relays against 4 kVA surges as described in IEC-61000-4-5.
3.4.3 Power supply and start
Do not connect the starter motor relay and the stop solenoid directly to the output terminals on the controller.
NOTE
Remember to mount the freewheeling diodes.