Split phase application L1/L2 (3 wires)
Split phase application L1/L3 (3 wires)
2.5.5

Rotary actuator outputs

The actuator outputs are used when a 4-wired rotary actuator is installed in your application. The integrated electronic
governor in the SGC controller is used together with the actuator to create an electronic governing application for
mechanical fuel engines. In diesel engines, the shaft output in the actuator is mechanically connected to a stop lever or the
throttle level in a fuel injection pump, for example. For petrol and natural gas engines, the shaft output is connected the
throttle or charge control valve.
Actuator connector outputs
2.5.6

Current transformer (CT) ground

Use one of these methods for the CT ground (S2) connections:
1. The S2 terminals are not grounded. The controller detects the current accurately.
2. The S2 terminals are grounded at the GND terminal (terminal 1).
User manual 4189341354A EN
SGC outputs
• ACT 1 is output terminal 17
• ACT 2 is output terminal 18
• ACT 3 is output terminal 19
• ACT 4 is output terminal 20