Digital Inputs; Analogue Inputs - Deif SGC 121 User Manual

Single genset controller
Hide thumbs Also See for SGC 121:
Table of Contents

Advertisement

Auto Exercise – Event 2 (AUTO EXERCISE – 2)
Parameter
Auto Exercise
(EVENT 2)
Event Occurrence
(EVENT OCCURENCE)
Event Day
(EVENT DAY)
Start Time
(START TIME)
Duration
(GEN ON DURATION)
Load Transfer
(LOAD TRANSFER)
3.5.2

Digital inputs

Digital Input # (DIG IN #)
Parameter
Source
(SOURCE)
Name
(NAME)
Polarity
(POLARITY)
Action
(ACTION)
Activation
(ACTIVATION)
Activation Delay
(ACTIVATION DELAY)
3.5.3

Analogue inputs

Analogue Input 1 (ENG TEMP / DIG G)
Parameter
Use Input As
(SENSOR SELECTION)
User manual 4189341354A EN
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
00:00 to 23:59 hour
00 hr 01 min. to 99 hr
59 min.
Enable
Disable
Range
See Digital input
source selection in
this document
Auxiliary Input #
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
0 to 60 s
Range
Not used
Digital Input G
Default
Not enabled
Daily
Runs every day
09:59 hours
10 hours, 10 minutes
Not enabled
Default
-
-
Close to Activate
None
From Monitoring On
1 s
Default
Not used
Description
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Configure how often the sequences occur.
Configure the start date for the sequences.
Configure the start time for the sequences.
Configure for how long the genset operates
during the scheduled sequences.
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
Description
Select an input source from the list.
You can configure the name of the input.
You can select how to activate the input. It can
be open or close with reference to ground.
You can configure what action occurs when the
digital input is activated.
You can configure when the controller starts to
monitor the digital input.
When the timer expires, the configured action
occurs.
Description
Select the input.
Page 22 of 72

Advertisement

Table of Contents
loading

Table of Contents