Make sure the grounding cable of the chassis is reliably
grounded. For information about how to connect the
grounding cable, see
Make sure the grounding terminal of the AC power receptacle is reliably grounded.
Connect the AC power supply to a power strip with lightning protection to enhance the lightning
protection capability of the power supply.
Install a surge protector at the input end of outdoor signal lines (for example, E1/T1 line) to
which interface modules of the router are connected to enhance the lightning protection
capability.
For information about how to install a power strip with lightning protector and surge protector, see
"Connecting the AC power supply to a power strip with lightning
protector
(optional)."

Space

For easy installation and maintenance, follow these space requirements:
Reserve a minimum of 1 m (3.28 ft) of clearance between the rack and walls or other devices.
For heat dissipation, make sure the headroom in the equipment room is not less than 3 m (9.84
ft).
Make sure the rack has enough space to accommodate the router. See
requirements. For more information about chassis dimensions, see H3C SR6604[6608]
Routers Hardware Information and Specifications.
Table1-6 Router dimensions and rack requirements
Model
SR6604 AC
SR6604 DC
SR6608 AC
SR6608 DC
SR6608-DS
"Grounding the
Chassis dimensions
Height—220 mm (8.66 in)/5 RU
Width—436 mm (17.17 in)
Depth—576 mm (22.68 in)
480 mm (18.90 in) for the chassis
95 mm (3.74 in) for the cable
management brackets at the chassis
front
11 mm (0.43 in) for the grounding screw
at the chassis rear
Height—308 mm (12.13 in)/7 RU
Width—436 mm (17.17 in)
Depth—576 mm (22.68 in)
480 mm (18.90 in) for the chassis
95 mm (3.74 in) for the cable
management brackets at the chassis
front
11 mm (0.43 in) for the grounding screw
at the chassis rear
Height—308 mm (12.13 in)/7 RU
Width—436 mm (17.17 in)
Depth—576 mm (22.68 in)
480 mm (18.90 in) for the chassis
95 mm (3.74 in) for the cable
management brackets at the chassis
router."
protection" and
Rack requirements
A minimum of 95 mm (3.74 in)
between the front rack posts and the
front door
A minimum of 481 mm (18.94 in)
between the front rack posts and the
rear door
A minimum of 0.8 m (2.62 ft) in depth
(recommended)
A minimum of 95 mm (3.74 in)
between the front rack posts and the
front door
A minimum of 481 mm (18.94 in)
between the front rack posts and the
6
"Installing a surge
Table1-6
for rack
A minimum of 0.8 m (2.62 ft) in
depth (recommended)
A minimum of 95 mm (3.74 in)
between the front rack posts and
the front door
A minimum of 481 mm (18.94 in)
between the front rack posts and
the rear door
A minimum of 0.8 m (2.62 ft) in
depth (recommended)