Make sure the grounding cable of the chassis is well grounded. For how to connect the
grounding cable, see
Make sure the grounding terminal of the AC power receptacle is well grounded.
Install a lightning arrester at the input end of the power supply to enhance the lightning
protection capability of the power supply.
Install a special lightning arrester at the input end of outdoor signal lines (for example, E1 line)
to which interface modules of the router are connected to enhance the lightning protection
capability.
For how to install lightning protectors and surge protector, see
power strip with lightning

Space

For easy installation and maintenance, follow these space requirements:
Reserve a minimum of 1 m (3.28 ft) of clearance between the rack and walls or other devices.
For heat dissipation, make sure the headroom in the equipment room is not less than 3 m (9.84
ft).
Make sure the rack has enough space to accommodate the router. See
requirements. For more information about chassis dimensions, see H3C
SR6604-X/SR6608-X/SR6616-X Routers Hardware Information and Specifications.
Table1-5 Router dimensions and rack requirements
Model
SR6604-X AC
SR6604-X DC
SR6608-X AC
SR6608-X DC
SR6616-X AC
SR6616-X DC
"Grounding the
protection" and
Chassis dimensions
Height—220 mm (8.66 in)/5 RU
Width—436 mm (17.17 in)
Depth—576 mm (22.68 in)
480 mm (18.90 in) for the chassis
95 mm (3.74 in) for the cable
management brackets at the chassis
front
11 mm (0.43 in) for the grounding screw
at the chassis rear
Height—308 mm (12.13 in)/7 RU
Width—436 mm (17.17 in)
Depth—576 mm (22.68 in)
480 mm (18.90 in) for the chassis
95 mm (3.74 in) for the cable
management brackets at the chassis
front
11 mm (0.43 in) for the grounding screw
at the chassis rear
Height—886 mm (34.89 in)/20 RU
Width—436 mm (17.17 in)
Depth—591 mm (23.27 in)
480 mm (18.90 in) for the chassis
102 mm (4.02 in) for the cable
management brackets at the chassis
front
11 mm (0.43 in) for the grounding screw
at the chassis rear
router."
"Connecting the AC power supply to a
"Installing a surge
protector."
Rack requirements
As a best practice, use a rack a
minimum of 0.8 m (2.62 ft) in depth.
As a best practice, use a rack a
minimum of 0.8 m (2.62 ft) in depth.
As a best practice, use a rack a
minimum of 0.8 m (2.62 ft) in depth.
7
Table1-5
for rack
A minimum of 95 mm (3.74 in)
between the front rack posts and the
front door.
A minimum of 481 mm (18.94 in)
between the front rack posts and the
rear door.
A minimum of 95 mm (3.74 in)
between the front rack posts and the
front door.
A minimum of 481 mm (18.94 in)
between the front rack posts and the
rear door.
A minimum of 102 mm (4.02 in)
between the front rack posts and the
front door.
A minimum of 490 mm (19.29 in)
between the front rack posts and the
rear door.