1MRS756014
5.4.1.
5.4.2.
5.5.
Ethernet Adapter
Modbus/TCP Brigde
Installation and Commissioning Manual
Adding Device object
To build the object tree:
1. Add a SPAZC40x_MODBUS Device object in the communication
structure by selecting the project name.
In the example the project Protocol Test is selected.
2. Right-click Protocol Test
3. Select New > Tunneling > SPAZC40x_MODBUS, see Fig. 5.4.1.-1.
A project can contain several Tunneling Device objects, for example all
substation feeder configurations and exported communication must be done
separately for each device.
Fig. 5.4.1.-1
Adding a Tunneling Device object
Ensure that the new IED name is unique within the planned network by
renaming the IED, for example REF545_F1.
A Tunneling Device object cannot be configured for an IEC
61850 gateway.
Adding Logical Device objects
For a Tunneling Devices, there is no need to add Logical Devices inside the
parent object. Logical devices LD0 and LD1 are already included to maintain
the SCL compatibility.
Configuring by using imported CID file
If you have to configure several SPA-ZC 400 with the similar settings, it is
possible to import a previously generated CID file and change the
communication addresses, typically by changing the IP address.
SPA-ZC 400
A051852
27