Adding Device Object; Adding Logical Device Objects - ABB SPA-ZC 402 Installation And Commissioning Manual

Spa tcp bridge
Table of Contents

Advertisement

1MRS756019
5.5.1.
5.5.2.
Ethernet Adapter
SPA/TCP Bridge
Installation and Commissioning Manual
3. Logical Node objects
4. Data objects

Adding Device object

To build the object tree:
1. Add a SPAZC40x_SPA Device object in the communication structure by
selecting the project name.
In the example, the project Protocol Test is selected.
2. Right-click Protocol Test
3. Select New > Tunneling > SPAZC40x_SPA, see Fig. 5.5.1.-1.
A project can contain several tunneling device objects, for example all substation
feeders.
Fig. 5.5.1.-1
Adding a Tunneling Device object
Ensure that the new IED name is unique within the planned network by renaming
the IED, for example REF545_F1.
A Tunneling Device object cannot be configured for an IEC 61850
gateway.

Adding Logical Device objects

For tunneling devices, there is no need to add logical devices inside the parent
object. Logical devices LD0 and LD1 are already included to maintain the SCL
compatibility.
SPA-ZC 402
SPA-ZC 402
A051859
27

Advertisement

Table of Contents
loading

Table of Contents