Encapsulated Interface Transport / Read Device Identification - ABB FSCA-01 User Manual

Rs-485 adapter module
Hide thumbs Also See for FSCA-01:
Table of Contents

Advertisement

72 Communication protocol
Function
code
10h
Write Multiple Registers
17h
Read/Write Multiple
Registers
2Bh/0Eh
Encapsulated Interface
Transport / Read Device
Identification
Encapsulated interface transport / Read device
identification
The adapter module supports the Modbus EIT/RDI objects shown
below.
Object ID
00h
Vendor Name
01h
Product Code
02h
Major/Minor Revision
03h
Vendor URL
04h
Product Name
Name
Description
Writes the contents of a
contiguous block of holding
registers in a server device.
Writes the contents of a
contiguous block of holding
registers in a server device, then
reads the contents of a
contiguous block of holding
registers (same or different than
those written) in a server device.
Allows reading identification and
other information of the server.
Parameter "Read Device ID code"
allows to define three access
types:
• 01: Request to get the basic
device identification (stream
access)
• 02: Request to get the regular
device identification (stream
access)
• 04: Request to get one specific
identification object (individual
access).
Name