Adding Device object

To build the object tree:
1. Add an IEC 61850 Device object in the communication structure by selecting the
project name.
2. Right-click Protocol Test
3. Select New > IEC 61850 > SPAZC40x_v2x, see Fig. 6.4.1.-1.
Normally, the SPAZC40x_v2x template from the menu is used. Only if the
connected SPA-ZC 402 is an older version 1.1.1, you have to select its own IED
template SPAZC40x_v1x from the menu. This is illustrated in the following figure.
A project can contain several IEC 61850 device objects, for example all substation
feeder configurations and exported communication must be done separately for each
device.
Fig. 6.4.1.-1
Adding an IEC 61850 Device object
Ensure that the new IED name is unique within the planned network by renaming
the IED, for example REF545_F1.
A Tunneling Device object cannot be configured for an IEC 61850
gateway.
The Logical Device LD0 describes SPA-ZC 402 and includes the data objects for
diagnostics and description. All data sets and report control blocks (RCB) are
collected to LLN0.

Adding Logical Device objects

Communication Engineering Tool (CET) creates logical device LD0 automatically
for SPA-ZC 402 when creating a new IED. All datasets and reporting control blocks
(RCB) are grouped under LD0 for event handling. It has also basic logical nodes
and data objects for diagnostics and device information.
Do not change the name of the LD0.