7.3.5
Recording and Reporting
7.3.5.1 Event Recorders (Only SICAM P855)
Default Settings and Setting Ranges
Table 7-10
Parameter
Swell threshold
Dip threshold
Interruption threshold
Event hysteresis
Underfrequency threshold
Overfrequency threshold
Voltage unbalance threshold
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018
Event Recorders
Default Setting
110 %
90 %
5 %
2 %
1 %
1 %
5 %
Supply voltage
105 % to 140 % in 5-% steps
75 % to 95 % in 5-% steps
1 %, 2 %, 3 %, 5 %, 8 % 10 %
1 % to 6 % in 1-% steps
Frequency
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
0.1 % to 0.9 % in 0.1-% steps
1 % to 5 % in 1-% steps
Unbalance
1 % to 5 % in 1-% steps
7 Operation at Use of a PC
7.3 Configuration of the Device
Setting Range