9 Operation at Use of a PC
9.3 Configuration of the Device
9.3.6

Recording and Reporting

In the Configure tab, you can view and, if necessary, edit the settings for recording and reports. You can select
these parameters in the Recording and reporting menu in the navigation window. The menu contains the fol-
lowing elements:
Event recorder
Trigger management
Recorder parameters
Mains signaling voltage
Memory management
Report configuration
Recording parameters
Transient detection
9.3.6.1 Event Recorder
Default Settings and Setting Ranges
Table 9-14
Parameter
Swell threshold
Dip threshold
Interruption threshold
Hysteresis
Event detection mode
RVC threshold
RVC hysteresis
RVC event detection mode
Underfrequency threshold
192
Event Recorder
110 %
90 %
5 %
2 %
1)
ph-N
6 %
2)
3 %
3)
ph-N
1 %
Default Setting
Voltage event
105 % to 140 % in 5-% steps
75 % to 95 % in 5-% steps
1 %, 2 %, 3 %, 5 %, 8 % 10 %
1 % to 6 % in 1-% steps
ph-N
ph-ph
RVC event
1 % to 6 % in 1-% steps
0.5 % to 3 % in 0.5-% steps
ph-N
ph-ph
Frequency event
0.1 % to 1.0 % in 0.1-% steps and
1.0 % to 5.0 % in 1.0-%-steps
Setting Range
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019