Parameter assignment / addressing
5.3 Configuring PROFIBUS DP
5.3.2

Operating the SIMOTION D4x5-2 on PROFIBUS DP

PROFIBUS DP interface (X126, X136)
SIMOTION D4x5-2 has two interfaces for connection to the PROFIBUS DP. Transmission
rates up to 12 Mbit/s are possible. Both interfaces can be operated isochronously.
The X136 interface can also be used as an MPI interface.
As supplied, both PROFIBUS DP interfaces are preset as a master with address 2 and a
transmission rate of 1.5 Mbit/s. The PROFIBUS DP network is automatically created for this
setting.
However, other settings can also be configured. This requires that you configure the network
manually using HW Config and NetPro.
Note
Communication with the SINAMICS Integrated of a D4x5-2 or CX32-2 is always
isochronous. Here, SIMOTION D4x5-2 is the master and the SINAMICS Integrated drives
are slaves.
Master-slave configuration
The master/slave configuration can be used, for example, to establish hierarchical
PROFIBUS networks that can be used to implement a modular machine concept.
Table 5- 1
Master-slave configuration
X126
X136
DP
DP/MPI
DP slave,
DP master,
isochronous
isochronous
DP master,
DP slave,
isochronous
isochronous
DP slave,
DP master, not
isochronous
isochronous
DP master, not
DP slave,
isochronous
isochronous
DP master,
DP master,
isochronous
isochronous
122
Remark
Application synchronized to DP master (X136), application
controls synchronization to DP slave (X126)
Internal drive is synchronous with external cycle clock
Cycle clock X136 = cycle clock DP Integrated
Application synchronized to DP master (X126), application
controls synchronization to DP slave (X136)
Internal drive is synchronous with external cycle clock
Cycle clock X126 = cycle clock DP Integrated
Application synchronized to DP slave (X126)
(can be monitored by the application)
Internal drive is synchronous with X126
Application synchronized to DP slave (X136)
(can be monitored by the application)
Internal drive is synchronous with X136
Application synchronized to DP master (X126, X136)
Internal drive is synchronous with external cycle clock
Cycle clock X126 = cycle clock X136 = cycle clock DP
Integrated
Commissioning and Hardware Installation Manual, 02/2012
Actions in the application
DP master / DP slave
synchronization
mechanisms
DP master / DP slave
synchronization
mechanisms
DP slave
synchronization
mechanisms
DP slave
synchronization
mechanisms
None
SIMOTION D4x5-2