Editing Sinamics Components; Downloading A Project To The Simotion D4X5-2 - Siemens SIMOTION D4 5-2 Series Commissioning And Hardware Installation Manual

Hide thumbs Also See for SIMOTION D4 5-2 Series:
Table of Contents

Advertisement

Commissioning (software)
6.3 Performing an online configuration for the D4x5-2
6.3.4

Editing SINAMICS components

Requirement
● You have loaded all connected DRIVE-CLiQ components to your user project.
● You have shut down the connection to the target system (offline mode).
Procedure
You can now adapt your components to the application.
Run through the wizard for all the DRIVE-CLiQ components to be adapted and perform the
required reconfigurations.
This procedure corresponds with the description in Performing the configuration for the
D4x5-2 offline (Page 159).
The amount of editing work involved depends on the components used. For example, in the
case of a motor with a DRIVE-CLiQ interface, the motor and encoder type are identified
automatically.
6.3.5

Downloading a project to the SIMOTION D4x5-2

After you have performed the reconfigurations, you must download the configuration to the
SIMOTION D4x5-2 (incl. SINAMICS Integrated).
1. Save and compile the project.
2. Go online.
3. To load the project, perform "Download project to target system".
192
The data must also be saved on the CompactFlash card to ensure that the project is
retained in the event of a power failure. The following options are available:
– Perform the "Copy RAM to ROM..." function manually on the D4x5-2 and all drives
(SINAMICS Integrated, CX32-2, etc.).
– In the "Download to Target System" dialog box, select the option "After loading, copy
RAM to ROM". You can change the default setting for this dialog box in "Options" >
"Settings" > "Download".
Commissioning and Hardware Installation Manual, 02/2012
SIMOTION D4x5-2

Hide quick links:

Advertisement

Table of Contents
loading