Commissioning (software)
6.18 Deleting data
Restoring factory settings with the mode selector switch
1. The power supply is switched off.
2. Set the mode selector on the SIMOTION D4x5-2 to MRES (switch position 3).
3. Switch on the power supply.
4. Now use the mode selector switch to change to the desired operating state.
Note
The communication parameters are now reset to the factory settings (PROFIBUS
address 2, baud rate of 1.5 Mbit/s). The communication configuration for
SIMOTION D4x5-2 must be performed again. The existing IP settings for the CBE30-2
are not restored to the factory settings.
290
The NVRAM and the SIMOTION user data is deleted. The factory settings are loaded.
SIMOTION D4x5-2 remains in STOP mode.
Commissioning and Hardware Installation Manual, 02/2012
SIMOTION D4x5-2