Connecting The Cx32-2 - Siemens SIMOTION D4 5-2 Series Commissioning And Hardware Installation Manual

Hide thumbs Also See for SIMOTION D4 5-2 Series:
Table of Contents

Advertisement

Connecting
3.5 Connecting DRIVE-CLiQ components
3.5.3

Connecting the CX32-2

Installation/Mounting/Wiring
Information on installing, mounting and wiring the CX32-2 can be found in the
D4x5-2
CX32-2 DRIVE-CLiQ topology
In contrast to other DRIVE-CLiQ components (e.g. terminal modules), special rules apply
when wiring the CX32-2.
● Only a point-to-point topology is possible between the CX32-2 and SIMOTION D. Each
● When a CX32-2 is inserted in an existing DRIVE-CLiQ connection (target port for CX32-2
● A CX32-2 is inserted via HW Config (see Section Configuration of a CX32-2 (Page 194)).
– To delete a CX32-2, it must be deleted from HW Config and then the configuration
– It is not possible to replace a control unit with six DRIVE-CLiQ ports (D435-2, D445-2
– The previous CX32 version cannot be used on a D4x5-2, see Section Permissible
56
Manual.
CX32-2 needs its own DRIVE-CLiQ port on the SIMOTION D control unit.
is occupied, e.g. by a TM31), this connection is disconnected and replaced by the
CX32-2 connection. The component that is freed up is moved to the component archive
of the SINAMICS topology overview. A notice is displayed indicating that the component
has been moved to the archive. The components must then be reassigned.
Whereby the selection made for the PROFIBUS address automatically and permanently
assigns the DRIVE-CLiQ port for connecting the CX32-2. Given that this assignment is
permanent, the following points must be noted:
– An inserted and configured CX32-2 cannot be connected to another DRIVE-CLiQ port
without taking additional measures. Reconnecting a CX32-2 results in a discrepancy
between the specified and actual topologies of the DRIVE-CLiQ components.
– A cross-exchange of two occupied DRIVE-CLiQ ports is not permitted. Such an
exchange results in inconsistencies in the specified-actual topologies.
– Once it has been created in HW Config, the connecting port of a CX32-2 cannot be
changed.
– To change the connecting port of a CX32-2, the CX32-2 must be deleted from HW
Config and recreated with another address.
saved and compiled.
or D455-2) with a control unit with four DRIVE-CLiQ ports (D425-2) when a CX32-2
has been configured with address 14 or 15 (a control unit with four DRIVE-CLiQ ports
does not have the DRIVE-CLiQ ports X104/X105 and consequently not the addresses
14 and 15).
combinations (Page 306) in Migration of D4x5 to D4x5-2.
Commissioning and Hardware Installation Manual, 02/2012
SIMOTION
SIMOTION D4x5-2