Connecting Ethernet; Wiring Ethernet - Siemens SIMOTION D4 5-2 Series Commissioning And Hardware Installation Manual

Hide thumbs Also See for SIMOTION D4 5-2 Series:
Table of Contents

Advertisement

Connecting

3.8 Connecting Ethernet

3.8
Connecting Ethernet
3.8.1

Wiring Ethernet

Procedure
To the 8-pin RJ45 sockets
● X127 P1
● X130 P1
● X120 P1 (only for D4x5-2 DP)
you can connect Industrial Ethernet.
The interfaces support a transmission rate of 10/100/1000 Mbit/s. Suitable Ethernet cables
and connectors must be used for the Ethernet connection.
Figure 3-13
Note
As of V4.3, the three Ethernet interfaces support the PROFINET basic services - they
therefore have the designation PN/IE-NET, PN/IE-OP or PN/IE.
These PROFINET basic services (e.g. DCP, LLDP, SNMP) provide uniform functions for the
address assignment and diagnostics, but do not provide PROFINET IO communication for
the connection of drives, I/O modules, etc.
72
Connecting Industrial Ethernet
Commissioning and Hardware Installation Manual, 02/2012