Connection Of The Power Unit; Ac Supply 230V / 1-Phase; Figure 7: Connection Of The Mains Supply 230 Vac / 1-Phase - KEB COMBIVERT G6M Instructions For Use Manual

Motor inverter
Table of Contents

Advertisement

4.2 connection of the Power Unit

Attention

4.2.1 Ac supply 230V / 1-phase

L1
N
PE
No.
Type
1
Mains voltage
Mains form
Personal protection
2
Main fuses
3
Mains contactor
4
Mains choke
5
KEB COMBIVERT
Figure 7:
Connection of the mains supply 230 VAC / 1-phase
Destruction of the drive converter!
► Never exchange mains input and motor output !
The terminal strips meet the requirements on IEC 60947-7-1
Some countries demand that the PE-terminal is directly connected to the termi-
nal box (not over the mounting plate).
TN, TT
RCMA with separator or RCD
type B
Type gG or MCCB
T1 T2
L1
N
PE
Description
1-phase 230 V AC
Earth leakage monitor
-
07Z1B02-1000 or 09Z1B02-1000
G6
U
V
W
PE
IT
-
33

Advertisement

Table of Contents
loading

Table of Contents