3.6.6 Sub-function 08 (0x08) Set type code

This sub-function code is used to set the type code of a module.
Request
00
Address
01
Function code
02
Sub function code 1 Byte
03
Reserved
04
Channel
05
Type code
Response
00
Address
01
Function code
02
Sub function code 1 Byte
03
Type code
Error Response
00
Address
01
Function code
02
Exception code
122
tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
1 Byte
1 to 247
1 Byte
0x46
0x08
1 Byte
0x00
1 Byte
0x00 ~ 0x07 for tM-TH8
1 Byte
Type code, see Section 1.10 for
details.
1 Byte
1 to 247
1 Byte
0x46
0x08
1 Byte
0: OK
others: error
1 Byte
1 to 247
1 Byte
0xC6
1 Byte
03: type code out of range, channel
out of range, reserved bytes
should be filled with zero,
incorrect number of bytes
received