2.7 $AA5

Description:
Reads the reset status of a module.
Syntax:
$AA5[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
5
Command to read the module reset status
Response:
Valid Command:
Invalid Command: ?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
S
Reset status of the module
1: This is the first time the command has been
sent since the module was powered on.
0: This is not the first time the command has
been sent since the module was powered on,
which denotes that there has been no module
reset since the last $AA5 command was sent.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.