3.7 Modbus Address Mappings

Address Description
00257
Protocol, 0: DCON, 1: Modbus
00258
Modbus protocol, 0: RTU, 1: ASCII
00261
1: enable, 0: disable host watchdog
00267
Temperature scale,
Celsius
00269
Modbus data format, 0: hex, 1:
engineering
00270
Host watch dog timeout status, write 1
to clear host watch dog timeout status
00272
Write 1 to load factory calibration
parameters
00273
Reset status, 1: first read after
powered on, 0: not the first read after
powered on
10129 ~
Over/under range status of channel 0
10136
to 7
00129 ~
00136
30001 ~
Analog input value of channel 0 to 7
30008
40001 ~
40008
40257 ~
Type code of channel 0 to 7
40264
40385 ~
Resistance offset of channel 0 to 7 in
40392
0.1 ohms, valid range: 0 ~ 255
40449 ~
Temperature offset of channel 0 to 7
40456
in 0.1°C/°F, valid range: -128 ~ 127