Aarttttr(Data) - ICP DAS USA tM-TH8 User Manual

Table of Contents

Advertisement

tM-TH8

2.32 @AARTTttR(Data)

Description:
Reads the temperature associated with the input resistance
of a user-defined type.
Syntax:
@AARTTttR(Data)[CHKSUM](CR)
@
Delimiter character
AA
Address of the module to be read (00 to FF)
RT
Command to read the temperature associated
with the input resistance of a user-defined type
Ttt
tt represents the type code of the user-defined
type.
R(Data) The (Data) consists of seven decimal digits, or
five digits, decimal point and one additional
digit, to represent the input resistance.
Response:
Valid command:
Invalid command: ?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command or
invalid type code
AA
Address of the responding module (00 to FF)
(Data)
The (Data) consists of a +/- sign, three digits,
decimal point and two additional digits to
represent the temperature associated with the
input resistance.
tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
!AA(Data)[CHKSUM](CR)
95