tM-TH8
Response:
Valid command:
Invalid command: ?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: ~01I
Sets the soft INIT timeout value of module 01 and
returns a valid response.
Command: %0101000700
Attempts to change the Baud Rate of module 01 to
19200 without first altering the INIT * status. The
module returns an invalid response because the soft
INIT timeout value is 0.
Command: ~01T10
Sets the soft INIT timeout value of module 01 to 16
seconds and returns a valid response.
Command: ~01I
Sets the soft INIT of module 01 and returns a valid
response.
Command: %0101000700
Changes the Baud Rate of module 01 to 19200
without first altering INIT * status. The module
returns a valid response.
tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
!AA[CHKSUM](CR)
Response: !01
Response: ?01
Response: !01
Response: !01
Response: !01