Table of Contents

Advertisement

tM-TH8

2.18 $AAS1

Description:
Reloads the factory default calibration parameters,
including the internal calibration parameters.
Syntax:
$AAS1[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to have the default
parameters reloaded (00 to FF)
S1
Command to reload the factory default
calibration parameters
Response:
Valid command:
Invalid command: ?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: $01S1
Sends the command to reload the factory default
calibration parameters for module 01 and returns a
valid response.
66
tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
!AA[CHKSUM](CR)
Response: !01