Sub-Function 32 (0X20) Read Firmware Version - ICP DAS USA tM-TH8 User Manual

Table of Contents

Advertisement

tM-TH8
3.6.7 Sub-function 32 (0x20) Read firmware
version
This sub-function code is used to read the firmware version
information of a module.
Request
00
Address
01
Function code
02
Sub function code 1 Byte
Response
00
Address
01
Function code
02
Sub function code 1 Byte
03
Major version
04
Minor version
05
Build version
Error Response
00
Address
01
Function code
02
Exception code
tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
1 Byte
1 to 247
1 Byte
0x46
0x20
1 Byte
1 to 247
1 Byte
0x46
0x20
1 Byte
0x00 ~ 0xFF
1 Byte
0x00 ~ 0xFF
1 Byte
0x00 ~ 0xFF
1 Byte
1 to 247
1 Byte
0xC6
1 Byte
03: incorrect number of bytes
received
123