3.6 70 (0x46) Read/Write Module
Settings
This function code is used to read the settings of the module or
change the settings of the module. The following sub-function
codes are supported.
Sub-function Code Description
00 (0x00)
04 (0x04)
05 (0x05)
06 (0x06)
07 (0x07)
08 (0x08)
32 (0x20)
37 (0x25)
38 (0x26)
41 (0x29)
42 (0x2A)
If the module does not support the sub-function code specified in
the message, then it responds as follows.
Error Response
00 Address
01 Function code
02 Exception code
114
tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
Read the module name
Set the module address
Read the communication settings 3.6.3
Set the communication settings 3.6.4
Read the type code
Set the type code
Read the firmware version
Read the channel enable/disable
status
Set the channel enable/disable
Read the miscellaneous settings 3.6.10
Write the miscellaneous settings 3.6.11
1 Byte
1 to 247
1 Byte
0xC6
1 Byte
02: invalid sub-function code
Section
3.6.1
3.6.2
3.6.5
3.6.6
3.6.7
3.6.8
3.6.9