4

Analog Input Type and Data Format

Type Code
07
*1
08
*1
09
*1
0A
*1
0B
*1
0C
0D
1A
*1: Only available on the ZT-2017
*2: FSR (Full Scale Range)
 Analog Input Over/Under Range Readings
Engineering Units
% of FSR
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
Input Type
Engineering Units
+4 to +20
mA
Engineering Units
-10 to +10
V
Engineering Units
-5 to +5
V
Engineering Units
-1 to +1
V
Engineering Units
-500 to +500
mV
Engineering Units
-150 to +150
mV
Engineering Units
-20 to +20
mA
Engineering Units
0 to +20
mA
Over Range
Data Format
*2
% of FSR
2's Comp. Hex
*2
% of FSR
2's Comp. Hex
*2
% of FSR
2's Comp. Hex
*2
% of FSR
2's Comp. Hex
*2
% of FSR
2's Comp. Hex
*2
% of FSR
2's Comp. Hex
*2
% of FSR
2's Comp. Hex
*2
% of FSR
2's Comp. Hex
+9999.9
+999.99
+F.S.
-F.S.
+20.000
+04.000
+100.00
+000.00
FFFF
0000
+10.000
-10.000
+100.00
-100.00
7FFF
8000
+5.0000
-5.0000
+100.00
-100.00
7FFF
8000
+1.0000
-1.0000
+100.00
-100.00
7FFF
8000
+500.00
-500.00
+100.00
-100.00
7FFF
8000
+150.000
-150.00
+100.00
-100.00
7FFF
8000
+20.000
-20.000
+100.00
-100.00
7FFF
8000
+20.000
+00.000
+100.00
+000.00
FFFF
0000
Under Range
-9999.9
-999.99
Page 25