the close loop output value has two actions for selection.
0: It must be consistent with the setup running direction: When the output value of the close loop
adjustment is inconsistent with the current setup running direction, the current output value will be forced
to be 0 internally.
1: It can be reverse to the setup running direction: When the output value of the close loop adjustment is
inconsistent with the current setup running direction, the close loop adjustment opposite to the current
setup running direction will be executed.
P8.09
PID is positeve function at default. Negative function is needed if the frequency is required to be
increased when feedback value is greater than reference value. This function can realized through
setting P8.09=1 or multi−function terminal function setting as 68.
P8.09=0, Terminal function is disabled: Positive;
P8.09=1, Terminal function is enabled: Positive;
P8.09=1, Terminal function is disabled: Negative;
P8.09=0,Terminal function is enabled: Negative.
P8.10

6.10 Motor Parameter (Group P9)

P9.00
This function is used to determine the motor load type driven by the inverter.
0: G−type constant torque/heavy−duty application
1: L−type variable torque/light−duty application
P9.01
P9.02
P9.03
P9.04
P9.01 ~ P9.04 are used to set the motor parameters driven by the setup inverter and shall be set
properly in accordance with the motor nameplate prior to the use.
Note: The power level of the inverter shall match the motor.
P9.05
P9.15
It determines the key motor parameters affecting the running control of the inverter through perform the
parameter auto−tuning. These motor parameters will be stored in the inverter automatically upon
completion of parameter auto−tuning process till next parameter input or another parameter auto−tuning.
The process of parameter auto−tuning is described as follows:
E5−H High Performance Universal Inverter
PID positive or negative function
Reserved
Load Type
Number of motor poles
Rated rotation velocity of motor
Rated power of motor
Rated current of motor
Motor no-load current I0
Parameter auto-tuning
Chapter 6 Parameter Description
User Manual
0 ~ 1 (0)
0 ~ 65535 (0)
0 ~ 1(0)
2~ 24(4)
0 ~ 30000 rpm(1500rpm)
0.4 ~ 999.9 kW(Factory)
0.1 ~ 999.9 A(Factory)
0.1 ~ 999.9 A (Factory)
0~1(0)
87