Safety Precautions Description of safety labels: Danger: If not avoided, could result in death, serious injury and considerable damage to property. Note: If not avoided, may cause minor or moderate injury and equipment damage. Danger Danger This series of inverter is used to control the three−phase motor and cannot be used for single−phase motor or other applications.
Page 3
Wiring Danger Danger The wiring must be conducted by qualified electricians. Otherwise, electric shock may happen or inverter may be damaged. Before wiring, confirm that the power supply is disconnected. Otherwise, electric shock may happen or fire. ...
Page 4
Operation Danger Danger Power supply can only be connected after the wiring is completed and the cover is installed. It is forbidden to remove the cover in live condition; otherwise, electric shock may happen. When automatic fault reset function or restart function is enabled, isolation measures shall be taken for the mechanical equipment, otherwise, personal injury may be caused.
Page 5
Note Note The circuit boards have large scale CMOS IC. Please do not touch the board to avoid the circuit board damage caused by ESD. Others Danger Danger It is forbidden to modify the inverter unauthorizedly; otherwise, human injury may be caused.
Control Mode Setting Process T. Setting Process for Motor Data Identification Motor data identification at standstill Complete motor data identification...
Contents Safety Precautions ............................i Control Mode Setting Process ........................iv Chapter 1 Product Information ....................... 1 T.T Product Model Description ........................T T.T Product Nameplate Description ......................T T.3 Product Series ............................T T.4 Technical Specifications of Product ......................3 T.5 Product Component Name ........................
Page 13
8.T Periodic Maintenance ......................... T3T 8.3 Component Replacement ........................T3T 8.4 Insulation Test ............................. T3T Appendix A Modbus Communication Protocol ................. 134 Appendix B E5 Series Hardware Non-standard List ................. 141 Appendix C EX−DT01 Digital Terminal Extension Card ..............142...
E5 Series High Performance Universal Inverter User’s Manual Chapter 1 Product Information T.T Product Model Description The digits and letters in the inverter model field on the nameplate indicate such information as the inverter series, input voltage, power, software version and hardware version.
E5 Series High Performance Universal Inverter User’s Manual T.3 Product Series □□□ E5−H−4T Three−phase 400V constant torqueTheavy−load application Power (kW) 0.75 T8.5 Motor 0.75 T8.5 power (kW) Voltage (V) Three−phase 0 to rated input voltage Rated current (A) Output T50% T minute, T80% T0 seconds, T00% 0.5 second, interval: T0 minutes (inverse time lag...
Page 16
E5 Series High Performance Universal Inverter User’s Manual □□□ E5−A−4T Three−phase 400V variable torqueTlight−load application Power (kW) T8.5 Motor T8.5 power (kW) Voltage (V) Three−phase 0 to rated input voltage Output Rated current (A) Overload capacity TT0% T minute, T0 minutes (inverse time lag feature) Rated Three−phase 380VT480V;...
E5 Series High Performance Universal Inverter User’s Manual T.4 Technical Specifications of Product Control mode Enhanced VTF control 0.50Hz T80% Starting torque Control Range of speed T:T00 characteristics regulation Precision of steady ± 0.5% speed Under-voltage regulation, switchover of run command source(operation panel, terminal and communication), speed tracing function, multi−...
Page 18
E5 Series High Performance Universal Inverter User’s Manual Power supply under-voltage, over-current protection, over-voltage protection, interference protection, abnormal comparison level, motor data identification failure, module(IPM) protection, heat-sink over temperature protection, inverter overload protection, motor overload protection, peripheral protection, abnormal current detection, output short circuit to ground, interruption of power supply when in running...
E5 Series High Performance Universal Inverter User’s Manual 1.7 Operation Panel Outline and Mounting Dimension Shuttle type operation panel (V6−DP01) Key type operation panel (V6−DP02) Rear view of operation panel Figure1−3 Operation panel outline and mounting dimension Note: E5−H−4T7.5G and below power class: Equipped with V6−DP01 as standard.
E5 Series High Performance Universal Inverter User’s Manual Chapter 2 Mechanical Installation T.T Environment for Product Installation Do not install the inverter in the sites with oil mist, metal powder and dust. Do not install the inverter in the sites with hazardous gas and liquid, and corrosive, combustible and explosive gas.
E5 Series High Performance Universal Inverter User’s Manual Above 200mm Air circulation position Air circulation Above 200mm position Above 200mm Air circulation position Air circulation Above 200mm position Above 100mm Above 100mm Above 100mm Above 100mm Figure T−T Mounting direction and clearance for E5−H−4TTTG T E5−A−4TT5 and above power class T.3 Removal and Mounting of Operation Panel and Cover...
Page 26
E5 Series High Performance Universal Inverter User’s Manual T.3.T Removal and Mounting of Covers with Plastic Enclosure Removal of operation panel Please refer to T.3.T Removal and Mounting of Operation Panel. Removal of lower cover After removing the mounting screws of the cover, press the left and right sides of the cover forcefully in direction T and lift the cover in direction T simultaneously, as shown in Figure T−5.
Page 27
E5 Series High Performance Universal Inverter User’s Manual T.3.3 Removal and Mounting of Covers with Sheet−metal Enclosure: E5−H−4TTTG, E5−H−4TT5G, E5−H−4TT8.5GA ~ E5−H−4T75GA E5−A−4TT5 ~ E5−A−4T90 Removal of operation panel Please refer to T.3.T Removal and Mounting of Operation Panel.
Page 28
E5 Series High Performance Universal Inverter User’s Manual T.3.4 Open and Close of Doors with Sheet−metal Enclosure: E5−H−4T90G and Above Power Class E5−A−4TTT0 and Above Power Class Opening of the door Press the latch following direction T in FigureT−TT and open the door following direction T.
E5 Series High Performance Universal Inverter User’s Manual Chapter 3 Electrical Installation 3.T Connection of the Inverter and Peripheral Devices Figure3−T Connection diagram of the product and peripheral devices Chapter 3 Electrical Installation...
E5 Series High Performance Universal Inverter User’s Manual 3.T Description of Peripheral Electrical Devices The circuit breaker capacity should be T.5 ~ T times of the inverter rated current. Circuit breaker The time features of the circuit breaker should fully consider the time features of the inverter overload protection.
E5 Series High Performance Universal Inverter User’s Manual 3.5 Functions of Main Circuit Terminal 3.5.T E5−H−4T0.75G ~ E5−H−4TT5G and E5−A−4TT.5 ~ E5−A−4TT8.5 Terminal symbol Terminal name and function description R/L1, S/L2, T/L3 Three−phase AC input terminal ⊕ ⊕ 2/B1 DC reactor connecting terminal, short circuited with copper bus by default ⊕...
E5 Series High Performance Universal Inverter User’s Manual 3.6 Attention for Main Circuit Wiring 3.6.T Power Supply Wiring It is forbidden to connect the three phase power supply cable to the inverter output terminals; otherwise, the internal components of the inverter will be damaged.
Page 35
E5 Series High Performance Universal Inverter User’s Manual 3.6.4 Countermeasures for Conduction and Radiation Interference Shielded Inverter cable Input filter Figure3−4 Noise current illustration When the input noise filter is installed, the wire connecting the filter to the inverter input power ...
E5 Series High Performance Universal Inverter User’s Manual 3.7 Terminal Wiring 3.7.T E5−H Figure3−6 Terminal wiring diagram (take E5−H−4T5.5G as an example) Chapter 3 Electrical Installation...
Page 37
E5 Series High Performance Universal Inverter User’s Manual 3.7.T E5−A T E5−H−34 T E5−H−63 Figure3−7 Terminal wiring diagram (take E5−H−4T5.5G−34 as an example) Chapter 3 Electrical Installation...
E5 Series High Performance Universal Inverter User’s Manual 3.8 Functions of Control Circuit Terminals 3.8.T E5−H Terminal Type Terminal function description Technical specification symbol Rate: 38400bps Up to 3T sets of equipment can be paralleled. Operation Relay shall be used if the number exceeds 3T.
Page 39
E5 Series High Performance Universal Inverter User’s Manual 3.8.T E5−A T E5−H−34 T E5−H−63 Type Terminal Description Technical specification Rate: 4800T9600TT9T00T38400T57600bps RS485+ Positive end of RS485 Up to 3T sets of equipment can be paralleled. Relay Terminal shall be used if the number exceeds 3T RS485−...
Page 40
E5 Series High Performance Universal Inverter User’s Manual 3.8.3 Wiring mode of the multi function digital input terminal and YTTYT output terminal Apply internal +T4V power supply, wiring in Apply external power supply, wiring in NPN sink current wiring mode...
E5 Series High Performance Universal Inverter User’s Manual 3.9 Schematic Diagram of Control Board 3.9.T E5−H Figure3−8 Schematic diagram of control board of E5−H 3.9.T E5−A T E5−H−34 T E5−H−63 Operation panel interface Drive board interface Expansion board mounting hole...
E5 Series High Performance Universal Inverter User’s Manual Chapter 4 Operation Panel 4.T Introduction to Operation Panel Shuttle type operation panel (V6−DP0T) Key−type operation panel (V6−DP0T) Figure 4−T Operation panel 4.T Descriptions of Indicators Symbol of Name Descriptions Color Indicator...
E5 Series High Performance Universal Inverter User’s Manual 4.3 Description of Keys on Operation Panel Symbol Name Function Shuttle type Key type T.Enter each level of menu Programming key T.Confirm displayed data storage 3.Check parameters in sequence 4.Confirm changeover of the run command channel with M key T.Back to first level menu from second level menu;...
Page 45
E5 Series High Performance Universal Inverter User’s Manual Table 4−1 Multi−function key function selection and the meanings of MULTI indicator Value Meanings of MULTI setting Function Descriptions indicator (P2.01) M key is defined as no function. No function Normally Off: No function...
E5 Series High Performance Universal Inverter User’s Manual 4.4 Menu Style The menu style is T−level menu. 4.4.T Format of First Level Menu Parameters zone Group number Separation sign Index in group Figure 4−T Format of first level menu Dividing the first level menu ...
Page 47
E5 Series High Performance Universal Inverter User’s Manual Structure of first level menu Menu structure Figure 4−3 Structure of first level menu 4.4.T Format of Second Level Menu Data bit T Data bit T Decimal point Data bit 3 Data bit 4 Figure 4−4 Format of second level menu...
Page 48
E5 Series High Performance Universal Inverter User’s Manual 4.4.3 Menu Mode Value setting Operation Menu mode name Visible parameters (P0.02) panel display See the table 5.T for all Basic menu mode bASE parameters Quickly display the menu Fast menu mode...
Page 49
E5 Series High Performance Universal Inverter User’s Manual 4.4.4 Common Characters Displayed by LED Except the parameters in first and second level menus, the operation panel will also display the following characters as shown in the following table: Prompt Prompt...
Page 50
E5 Series High Performance Universal Inverter User’s Manual 4.4.5 Identify Symbols Displayed Via LED The relationship between characters displayed by LED and charactersTnumbers are as follows: Meanings of Meanings of Meanings of Meanings of LED display LED display LED display...
E5 Series High Performance Universal Inverter User’s Manual 4.5 Password Operation Set Password Enter password parameter P0.00 and set to the identical parameters for two times continuously. After “P.Set” is displayed, the password setting is successful. See 4.8.3 for password setting.
E5 Series High Performance Universal Inverter User’s Manual 4.7 Operation Panel Display and Key Operation 4.7.T Classification of Display Status There are 8 types of display status of operation panel: Status Meaning Press >> key to switch the displayed parameters Display parameters in stop status PT.03 can be used to set the displayed parameters...
E5 Series High Performance Universal Inverter User’s Manual 4.8 Operation Example In the following example, the displayed parameters in stop status is reference frequency, the factory setting is 50.00Hz. The underscored line in the figure means the bit that is being edited.
E5 Series High Performance Universal Inverter User’s Manual 4.9 Running for the First Time Please follow the procedures to run for the first time: Chapter 4 Operation Panel...
Used for recording parameters by user Note: E5 series built−in multiple control mode for fan and pump to realize customized energy saving requirement. For details, refer to the parameter descriptions of Pb.TT and Pb.TT. E5 series built in constant pressure control and sleep function. For details, refer to the parameter descriptions of −...
Page 56
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User 0: Operation panel Run command channel P0.06 0 ~ T ○ T: Terminal selection T: Communication Running direction 0: Run forward P0.07 0 ~ T ○...
Page 57
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Group P2 Key and Display Parameters 0: No locking Operation panel key− T: Locking all keys PT.00 locking function 0 ~ 3 ○ T: Locking all keys except MULTI key...
Page 58
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Group P3 Start/stop Parameters 0: Normal start P3.00 Start mode 0 ~ T × T: Start after DC injection T: Flying start E5−H: 0.0 ~ TT0.0% of inverter rated current P3.0T DC injection current...
Page 59
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Multi−step digital voltage P4.T5 T.00 0.00 ~ T0.00 ○ 0.00 ~ T0.00V reference T Multi−step digital voltage P4.T6 T.00 0.00 ~ T0.00 ○ 0.00 ~ T0.00V reference T Multi−step digital voltage...
Page 60
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User XT to X7 terminal filter P5.07 0.T00 0.000 ~ T.000 × 0.000 ~ T.000s time P5.08 XT terminal delay time 0.0 ~ 999.9 × P5.09 XT terminal delay time 0.0 ~ 999.9...
Page 61
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User P6.T5 Curve4 input point AT T5.0 0.0 ~ TT0.0 ○ 0.0 ~TT0.0% Per unit value BT P6.T6 corresponding to curve4 T5.0 0.0 ~ TT0.0 ○...
Page 62
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Ones place: AOT gain: 0: Positive T: Negative Tens place: AOT bias: Positive logic or 0: Positive T: Negative P7.09 negative logic selection 0000 0 ~ TTTT ○...
Page 63
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Group P8 PID Close Loop Control parameters Analog feedback process close loop Digital voltage reference for process close loop P8.00 0.00 0.00 ~ T0.00 ○...
Page 64
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Ones place: Protection mode: 0: Motor current mode T: Sensor mode P9.T6 Motor overload protection 00 ~ TT × T: Inactive Tens place: Low speed de-rated:...
Page 65
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Ones place: Detected mode selection: 0: Motor overload pre−alarm, relative to motor rated current T: Inverter overload pre−alarm, relative to inverter rated current Inverter or motor PA.T3...
Page 66
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User UPTDN single step Pb.06 frequency setting 0.T0 0.00 ~ T0.00 ○ 0.00 ~ T0.00Hz without integral function Ones place: Acceleration T deceleration time: 0: XT...
Page 67
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Pb.T7 Preset frequency 0.00 0.00 ~ 300.00 ○ 0.00 ~ 300.00Hz Preset frequency Pb.T8 0.0 ~ 3600.0 ○ 0.0 ~ 3600.0s operating time Pb.T9 Wake-up frequency 0.00...
Page 68
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Group PE Controlled by Manufacture Parameters 1 PE.00 Reserved 0000 ~ FFFF ○ PE.06 Oscillation suppression PE.07 0004 0 ~ 65535 ○ parameter T Oscillation suppression PE.08...
Page 69
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Software version of dT.04 Factory 0.000 ~ F.FFF 0.000 ~ F.FFF extension card dT.05 Manufacture bar code T Factory 0 ~ 9999 0 ~ 9999 dT.06 Manufacture bar code T Factory...
Page 70
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User Group H0 Special Parameters for Constant Pressure Control Process closed loop function selection for 0: Disabled H0.00 0 ~ T × constant pressure T: Enabled...
Page 71
E5 Series High Performance Universal Inverter User’s Manual Name Default Range Unit Property Description User 0: Positive logic is active T: Negative logic is active bit0: X8 positive logic or negative logic selection X8~XTT terminal HT.07 positive logic or negative 0 ~ F ○...
E5 Series High Performance Universal Inverter User’s Manual Chapter 6 Parameter Descriptions 6.T Basic Function Parameters (Group P0) P0.00 User password 0000 ~ FFFF (0000) In order to prevent the irrelevant personnel from querying and changing the parameters, and protect your know-how, it is possible to restrict access to the parameters by setting user password.
Page 73
E5 Series High Performance Universal Inverter User’s Manual Note: After commissioning is completed, to conveniently record and query the modified parameters. When perform on-site maintenance, to conveniently record and query the modified parameters. 3: Last changed T0 parameters menu mode: The last changed T0 parameters can be inquired.
Page 74
E5 Series High Performance Universal Inverter User’s Manual Open loop main reference channel P0.04 0 ~ 4(0) Open loop digital frequency reference P0.05 0.00 ~ 300.00 Hz(50.00Hz) This function is applicable to the frequency reference of open loop control mode (P0.03=0).
Page 75
E5 Series High Performance Universal Inverter User’s Manual Acceleration time 0 P0.08 0.T ~ 3600.0 s (6.0s or T0.0s) Deceleration time 0 P0.09 0.T ~ 3600.0 s (6.0s or T0.0s) S curve time P0.T0 0.0 ~ 60.0 s (0.0s) These parameters are used to set the acceleration time and deceleration time for acceleration and deceleration.
Page 76
E5 Series High Performance Universal Inverter User’s Manual Maximum output frequency P0.TT 0.0T ~ 300.00 Hz (50.00Hz) Maximum output voltage P0.TT T ~ 480 V (380V) Frequency upper limit P0.T3 0.00 ~ 300.00 Hz (50.00Hz) P0.T4 Frequency lower limit 0.00 ~ 300.00 Hz (0.00Hz) P0.T5...
E5 Series High Performance Universal Inverter User’s Manual 6.T Main and Auxiliary Reference Parameters (Group PT) Open loop auxiliary frequency reference channel PT.00 00 ~ T4(00) Open loop main frequency reference and auxiliary frequency PT.0T 0 ~ 5(0) reference calculation formula...
Page 78
E5 Series High Performance Universal Inverter User’s Manual T: Auxiliary reference−50%: The auxiliary reference value subtracts the bias equal to 50% of the auxiliary reference full range value. The main reference value is disable at this calculation formula. 3: Main reference + auxiliary reference−50%: The auxiliary reference value subtracts the bias equal to 50% of the auxiliary reference full range value and then superimposes on the main reference.
Page 79
E5 Series High Performance Universal Inverter User’s Manual Analog feedback close loop control main feedback channel PT.05 T ~ 4(T) Analog feedback close loop control auxiliary feedback channel PT.06 0 ~ 4(0) Analog feedback close loop control main feedback and auxiliary PT.07...
E5 Series High Performance Universal Inverter User’s Manual 6.3 Key and Display Parameters (Group PT) Operation panel key-locking function selection PT.00 0 ~ 3(0) This parameter is used to realize the keys locking function of operation panel, so as to avoid mis−operation.
Page 81
E5 Series High Performance Universal Inverter User’s Manual Display parameter selection in stop status PT.03 0000 ~ FFFF (3TT0) Up to 4 parameters can be set and displayed in stop status, and viewed circularly by pressing >> key. PT.0T Display parameter selection in stop status...
E5 Series High Performance Universal Inverter User’s Manual 6.4 StartTstop Parameters (Group P3) Start mode P3.00 0 ~ T(0) This parameter is used to set the start mode; start mode should be selected according to the actual situation. 0: Start to run from the start frequency P3.03 and accelerates to the setting frequency after the start frequency holding time P3.04.
Page 83
E5 Series High Performance Universal Inverter User’s Manual DC braking start frequency P3.06 0.00 ~ 300.00 Hz (0.00Hz) DC braking current P3.07 0.0 ~ TT0.0 %( 0.0%) DC braking active time P3.08 0.0 ~ 30.0 s (0.0s) P3.06 is used to set the DC braking start frequency during stopping.
Page 85
E5 Series High Performance Universal Inverter User’s Manual Acceleration time T P4.09 0.T ~ 3600.0 s (T0.0s) Deceleration time T P4.T0 0.T ~ 3600.0 s (T0.0s) Acceleration time T P4.TT 0.T ~ 3600.0 s (T0.0s) P4.TT Deceleration time T 0.T ~ 3600.0 s (T0.0s) P4.T3...
Page 86
E5 Series High Performance Universal Inverter User’s Manual Multi-step frequency reference T P4.TT 0.00 ~ 300.00 Hz (5.00Hz) Multi-step frequency reference T P4.T3 0.00 ~ 300.00 Hz (8.00Hz) Multi-step frequency reference 3 P4.T4 0.00 ~ 300.00 Hz (T0.00Hz) P4.T5 Multi-step frequency reference 4 0.00 ~ 300.00 Hz (T5.00Hz)
E5 Series High Performance Universal Inverter User’s Manual 6.6 Multi−function Input Parameters (Group P5) P5.00 Digital input terminal XT function selection 00 ~ 99(0T) P5.0T Digital input terminal XT function selection 00 ~ 99(03) Digital input terminal X3 function selection P5.0T...
Page 88
E5 Series High Performance Universal Inverter User’s Manual The following table lists the multi−function digital input terminal functions: Setting Setting Function Function value value Jog forward Stop via terminal with DC braking T Jog reverse Counter input Forward (FWD) Counter reset...
Page 89
E5 Series High Performance Universal Inverter User’s Manual 06: Multi−step digital voltage terminal T 07: Multi−step digital voltage terminal T 08: Multi−step digital voltage terminal 3 Refer to the parameter descriptions of P4.T5 ~ P4.TT. 09: Multi− step frequency terminal T T0: Multi−...
Page 90
E5 Series High Performance Universal Inverter User’s Manual T3: Stop via terminal When the inverter is in the running status, if this terminal change from OFF to ON (rising edge, terminal function from disabled to enabled), the motor will deceleration to stop. But it is important to note that if in stop status and this terminal keeps ON, the motor will run if receive run command.
Page 91
E5 Series High Performance Universal Inverter User’s Manual 49: Run command is changed to terminal 50: Run command is changed to communication The above three functions are set to change the run command channel. When the terminal is switched from OFF status to ON status, the rising edge trigger is enabled.
Page 92
E5 Series High Performance Universal Inverter User’s Manual XT to X7 terminal filter time P5.07 0.000 ~T.000 s (0.T00s) This parameter is used to improve the anti−interference capability of the multi-function digital input terminal. XT terminal delay time P5.08 0.0 ~ 999.9 s (0.0s) P5.09...
Page 93
E5 Series High Performance Universal Inverter User’s Manual P5.TT StartTstop mode selection 0 ~ 3(0) P5.TT is used to set the mode of controlling the start and stop of the inverter with FWD and REV terminals when run command reference mode is terminal.
Page 94
E5 Series High Performance Universal Inverter User’s Manual P5.TT Preset counting value setting 0000 ~ 9999(0000) P5.T3 Designated counting value setting 0000 ~ 9999(0000) When the pulse signal counting of the terminal input complies with the preset condition, the terminal Yi will output corresponding instructions.
E5 Series High Performance Universal Inverter User’s Manual 6.7 Analog Reference Parameters (Group P6) P6.00 AIT to AI3 and DI input curve selection 0000 ~ 4444(4444) This function is used to define the analog input range and target range. Four curves are provided for users.
Page 96
E5 Series High Performance Universal Inverter User’s Manual Figure6−T0 Percentage of input analog (voltageTpulse) Figure6−TT Percentage of input analog (current) Figure6−TT Reference frequency curve (positive) Figure6−T3 Reference frequency curve (negative) e.g. AIT input 4 ~ T0mA corresponding to 0 ~ 50Hz : T) First, check the AIT jumper if is switched to I side T) Setting P6.00 tens place to 0, select curve T...
Page 97
E5 Series High Performance Universal Inverter User’s Manual Curve 3 have a linear correspondence and curve 4 have four-point correspondence. The input analog characteristics curve as shown in the following figure. Curve 4 is described as an example here. Curves 3 and 4 convert the externally input analog into the internal value. All the AI and DI inputs will be converted to percentage.
Page 98
E5 Series High Performance Universal Inverter User’s Manual AIT filter time P6.TT 0.000 ~T.000 s (0.004s) AIT filter time P6.T3 0.000 ~T.000 s (0.004s) P6.T4 AI3 filter time 0.000 ~T.000 s (0.004s) The analog values input via AIT, AIT and AI3 terminals usually have certain interference signals. It can amplify the setup value of AI filter time properly to improve the anti−interference capability.
E5 Series High Performance Universal Inverter User’s Manual 6.8 Multi-Function Output Parameters (Group P7) P7.00 YT output function selection 00 ~ 47(00) P7.0T YTTDO output function selection 00 ~ 7T(0T) Relay output function selection P7.0T 00 ~ 47(T4) AOT output function selection P7.03...
Page 100
E5 Series High Performance Universal Inverter User’s Manual 04: Inverter or motor overload pre−alarm(OL) When the output current exceeds the PA.T4 (overload pre−alarm detection level) setting and lasts longer than PA.T5 setting (overload pre−alarm detection time), the signal is enabled. When the current is lower than PA.T4 setting, the signal is disabled.
Page 101
E5 Series High Performance Universal Inverter User’s Manual TT: Zero current detection arrival When the output current is lower than the zero current detection level, the signal is enabled. Refer to P7.T8 for details. T3: Stop command When the inverter is in the stop or standby status, the signal is enabled.
Page 103
E5 Series High Performance Universal Inverter User’s Manual Figure6−T7 AOT Characteristics Curve−Kx+b Figure6−T8 AOT Characteristics Curve−Kx+b Note: When the analog output both gain and bias are set to negative, the output will be limited to 0V. P7.T0 YTTDO maximum output pulse frequency 0.T ~ 50.0 kHz (T0.0 kHz)
Page 104
E5 Series High Performance Universal Inverter User’s Manual Figure 6−T9 Delay of output terminal Yi P7.T8 Zero current detection level 0.0 ~ 50.0 % (0.0%) This parameter is used to detect the load. If the output terminal is set to “TT: Zero current detection arrival”, the output will be active if the output current is lower than the zero current detection level P7.T8.
Page 105
E5 Series High Performance Universal Inverter User’s Manual Virtual terminal selection P7.T4 000 ~ T0T(000) It controls the action of the multi-function input terminal or output terminal by the host computer. P7.T4 Virtual terminal effective selection Multi-function input terminal Xi...
E5 Series High Performance Universal Inverter User’s Manual 6.9 Process PID Close Loop Parameters (Group P8) Analog feedback process close loop control digital voltage 0.00 ~ T0.00 V (0.00 V) P8.00 reference Single-phase pulse feedback process close loop control digital P8.0T...
Page 107
E5 Series High Performance Universal Inverter User’s Manual Proportional gain Kp P8.03 0.000 ~ T0.000(0.T00) Integral gain Ki P8.04 0.000 ~ T0.000(0.500) Derivative gain Kd P8.05 0.000 ~ T0.000(0.000) The larger the Kp value setting, the faster the response, but if the Kp value is too large, vibration may occur, and the deviation cannot be eliminated completely only by Kp.
Page 108
E5 Series High Performance Universal Inverter User’s Manual changes, before the integral value catch up that change trend, it needs to take longer time to offset the effect brought by the continuous integral . If the output value of the close loop regulation is inconsistent with the current setup running direction, the close loop output value has two actions for selection.
E5 Series High Performance Universal Inverter User’s Manual 6.T0 Motor Parameters (Group P9) Reserved P9.00 0 ~ T(0) P9.0T Motor poles T ~ TT8(4) P9.0T Motor rated speed 0 ~ 30000 rpm (T500rpm) P9.03 Motor rated power 0.4 ~ 999.9 kW (Factory) P9.04...
Page 110
E5 Series High Performance Universal Inverter User’s Manual is in the standstill status when starting data identification. If there is over current or over voltage fault during the data identification process, it can prolong the accelerationTdeceleration time P0.08 and P0.09 properly.
Page 111
E5 Series High Performance Universal Inverter User’s Manual Figure6−33 Motor overload protection characteristics curve (constant torque) T: Sensor mode. Compare the analog feedback value of the thermal sensor installed on the motor with the present sensor protection threshold P9.T7. If the feedback value is higher than that protection threshold, the inverter will report “E.Ptc”...
E5 Series High Performance Universal Inverter User’s Manual 6.TT Control Parameters (Group PA) Switching frequency PA.00 0.7 ~ T6.0 kHz (Factory) PA.0T Switching frequency automatic adjustment 0 ~ T(T) Switching frequency has an important impact on operations of inverter and motor. When switching frequency increases, the motor loss, motor temperature rising and motor noise will be decreased.
Page 113
E5 Series High Performance Universal Inverter User’s Manual If current limit function is enabled, when the current exceeds current limit level (PA.05), the inverter will turn into current limit status. If the current level drops below current limit value (PA.05), exit the current limit status automatically, then normal operation will continue.
Page 114
E5 Series High Performance Universal Inverter User’s Manual Magnetic flux braking selection PA.08 0 ~ T(T) 0: Magnetic flux braking is disabled T: Magnetic flux braking is enabled When the motor decreases, the motor can be rapidly decelerated if magnetic flux braking is selected. The energy of the mechanical system is changed to thermal energy in the motor during the braking process.
Page 115
E5 Series High Performance Universal Inverter User’s Manual Inverter or motor overload pre-alarm PA.T3 000 ~ TTT(000) Overload pre-alarm detection level PA.T4 T0.0 ~ T00.0 % (T30.0%) Overload pre-alarm detection time PA.T5 0.T ~ 60.0 s (5.0s) Overload pre-alarm function can realize indication of pre-setting overload status or alarm stop.
Page 116
E5 Series High Performance Universal Inverter User’s Manual Faults shield and alarm attribute setting T PA.T6 0000 ~ TTTT(00T0) Faults shield and alarm attribute setting T PA.T7 0000 ~ TTTT(00T0) Faults shield and alarm attribute setting 3 PA.T8 0000 ~ TTTT(T000) PA.T9...
Page 117
E5 Series High Performance Universal Inverter User’s Manual PA.T0 Fault locking function selection 0 ~ T(0) 0: Fault is not locked. T: Fault is locked: Allowing re-display faults that is occurred last power-off after power on, fault must be −...
E5 Series High Performance Universal Inverter User’s Manual 6.TT Enhanced Function Parameters (Group Pb) Jump frequency lower limit T Pb.00 0.00 ~ 300.00 Hz(0.00Hz) Jump frequency upper limit T Pb.0T 0.00 ~ 300.00 Hz(0.00Hz) Jump frequency lower limit T Pb.0T 0.00 ~ 300.00 Hz(0.00Hz)
Page 119
E5 Series High Performance Universal Inverter User’s Manual Operational panel ∧/∨ digital regulating frequency control Pb.08 0000 ~ 0TTT(000T) Operational panel ∧/∨ integral rate Pb.09 0.T ~ 50.0 s (T.0s) Through operational panel ∧T∨ to regulate frequency and the frequency value will be saved and superimposed on other frequency as final frequency.
Page 120
E5 Series High Performance Universal Inverter User’s Manual Terminal UPTDN digital regulating frequency control Pb.T0 0000 ~ TTTT(000T) Pb.TT 0.T ~ 50.0 s(T.0s) Terminal UPTDN integral rate Pb.T0 Terminal UPTDN digital regulating frequency control Save after power off 0: Saved after power-off...
Page 121
E5 Series High Performance Universal Inverter User’s Manual Automatic restart Pb.T5 0 ~ T(0) Automatic restart waiting time Pb.T6 0.0 ~ T0.0 s (0.5s) 0: Disabled T: Enabled After a power failure, the function supports automatic restart the unit if power on again. This function should be used judiciously.
Page 122
E5 Series High Performance Universal Inverter User’s Manual Fan and pump control mode selection Pb.TT 0 ~ 3(0) Forced energy saving rate reference Pb.TT 0 ~ 50% (T0%) The two parameters are used to set control mode for fan and pump.
E5 Series High Performance Universal Inverter User’s Manual 6.T3 Communication Parameters (Group PC) Note: Terminal 485 only available for “E5−H−4T**G−63”, “E5−H−4T**G−34” non−standard series and E5−A series. So group PC is used for above series. PC.00 Communication baud rate 4 ~ 8(5) PC.0T...
Page 124
E5 Series High Performance Universal Inverter User’s Manual Master-slave mode PC.04 0 ~ T(0) Operating Address from master to slave (set by master) PC.05 0 ~ T(0) Slave receive value proportional (set by slave) PC.06 0.00 ~ T0.00(T.00) PC.04 master−slave mode:...
E5 Series High Performance Universal Inverter User’s Manual 6.T5 Fault Record Parameters (Group d0) Fault record T d0.00 0 ~ 6T(0) d0.0T Fault record T 0 ~ 6T(0) d0.0T Fault record 0 (Latest) 0 ~ 6T(0) d0.03 Bus voltage of latest fault 0 ~ 65535 V (0V) d0.04...
E5 Series High Performance Universal Inverter User’s Manual 6.T6 Product Identity Parameters (Group dT) Serial number dT.00 0.0 ~ FFF.F (factory) dT.0T Software version of control board 0.00 ~ 99.99 (factory) dT.0T Software non-standard version of control board 0.00 ~ FF.FF (factory) dT.03...
Page 128
E5 Series High Performance Universal Inverter User’s Manual 6.T7 Display Parameters (Group dT) Heat-sink T temperature dT.00 0.0 ~ T00.0ºC (0.0ºC) dT.0T Terminal count value 0 ~ 65535 (0) dT.0T AIT percentage after curve transformation 0.0 ~ T00.0 % (0.0%) dT.03...
E5 Series High Performance Universal Inverter User’s Manual 6.T8 Special Parameters for Constant Pressure Control (Group H0) Close loop function selection for constant pressure control H0.00 0 ~ T(0) P0.03 Control mode 0 ~ 3(0) H0.00 is used to set the close loop mode for constant pressure control.
Page 130
E5 Series High Performance Universal Inverter User’s Manual Sleep frequency setting H0.06 0.00 ~ 300.00 Hz(30.00Hz) Sleep delay time H0.07 0.0 ~ 3600.0 s(60.0s) Wake up pressure percentage H0.08 0.0 ~ T00.0 %(50%) H0.09 Exit wake-up delay time 0.0 ~ 3600.0 s(30.0s)...
Page 131
E5 Series High Performance Universal Inverter User’s Manual When PID is set to negative function (setting P8.09 to T): If pressure feedback lower than sleep pressure setting (H0.3T), and last longer than sleep delay time (H0.34), the frequency decelerate to 0 Hz.
E5 Series High Performance Universal Inverter User’s Manual 6.T9 Special Parameters for EX-DT0T (Group HT) EX-DT0T digital terminal extension card selection HT.00 0 ~ T(T) If EX-DT0T card is installed, HT.00 should be set to T to enable the function of EX-DT0T.
E5 Series High Performance Universal Inverter User’s Manual 6.T0 Controlled by Manufacture Parameters T (Group A0) Reserved A0.00 0000 ~ FFFF(factory) A0.0T XT ~ X7, AIT ~ AI3 terminal positive logic or negative logic selection 0 ~ FFFF(03FF) A0.0T is used to set the positive logic or negative logic for XT to X7 and AIT to AI3. The default is 03FF, positive logic.
E5 Series High Performance Universal Inverter User’s Manual 6.TT Setting Process for Constant Pressure Control START Motor data identification (For details, refer to the parameter of P9.T5) P0.03=T (Process close loop ) H0.00=T (Constant pressure control) Pressure setting is analog? H0.04=0 (pressure setting is H0.05...
E5 Series High Performance Universal Inverter User’s Manual Chapter 7 Troubleshooting 7.T List of Fault and Alarm Information This chapter lists all the fault and alarm messages including the possible causes and corrective actions, Once a fault is detected, the following fault code will be displayed on the operation panel, the fault contact output operates, and the output to motor is disable, the motor will coast to stop.
Page 136
E5 Series High Performance Universal Inverter User’s Manual Fault Fault display Fault description Possible causes Corrective actions on panel Loose connection of connectors Ask professional technicians to inside the inverter maintain Abnormal Abnormal switching power supply Seek for technical support E.rEF...
Page 137
E5 Series High Performance Universal Inverter User’s Manual Fault Fault display Fault description Possible causes Corrective actions on panel Input power under voltage Check input power supply Start again after the motor at Start when motor is spinning standstill Keep overloading for a long period...
Page 138
E5 Series High Performance Universal Inverter User’s Manual Fault Fault display Fault description Possible causes Corrective actions on panel Abnormal connection, missing Check the three phase output connection or disconnection at the whether exits missing connection output side or disconnection...
Page 139
E5 Series High Performance Universal Inverter User’s Manual Fault Fault display Fault description Possible causes Corrective actions on panel The communication of terminal Check the connection of the RS485 is disconnected equipment communications The baud rate is set improperly Set compatible baud rate...
E5 Series High Performance Universal Inverter User’s Manual 7.3 FAQ Ⅰ. Why have abnormal operation? (T) Check if motor data identification has been performed. For details, refer to the parameter of P9.T5 (T) For E5−H series, check if the lines for Hall sensor is loosen or dislocated for E5−H−4TT8.5GA and above power class, for E5−A series, check if the lines for Hall sensor is loosen or dislocated for...
Page 142
E5 Series High Performance Universal Inverter User’s Manual . Why the host computer and inverter have abnormal communication? Ⅷ (T) Check if the data format, address and baud rate are consistent with the host computer (T) Check if the host computer address needs to be added by T (that is,”Address +T”)
Page 143
E5 Series High Performance Universal Inverter User’s Manual command. The fan will run when in running status or the heat-sink temperature reach fan running temperature. E5−A series: (T) T8.5kW and below power class: The fan will run after power on...
E5 Series High Performance Universal Inverter User’s Manual Chapter 8 Maintenance and Inspection The application environment (such as temperature, humidity, dust and powder, wool, smoke and oscillation), burning and wearing of internal devices and other factors may reduces the service life. To reduce the fault and prolong the service life, it is necessary to perform daily inspections and periodic maintenance.
E5 Series High Performance Universal Inverter User’s Manual 8.T Periodic Maintenance It needs to perform periodic maintenance every three to six months according to the application environment and work conditions. Item Inspection Contents Inspection Means Criteria The screws are tightened and the...
E5 Series High Performance Universal Inverter User’s Manual 8.4 Insulation Test Insulation test had been perform before leaving−factory, the user should not perform such test as much as possible under general condition. If the test is unavoidable, please perform the test strictly according to the following procedures, or inverter may be damaged.
E5 Series High Performance Universal Inverter User’s Manual Appendix A Modbus Communication Protocol T. Support Protocol Support Modbus RTU protocol, broadcast address is 0, the slave address range isT to T47, T48 to T55 is reserved. T. Interface mode RS485: Asynchronous, half duplex, LSB sending priority. Low byte is follow the high byte.
Page 148
E5 Series High Performance Universal Inverter User’s Manual Abnormal codes: Abnormal Abnormal Definition Definition code code Frame error: frame length error, check sum 0x0T Illegal command 0xT0 error 0x0T Illegal data address 0xTT Parameters are unchangeable Illegal data, data beyond upper limit or...
Page 149
E5 Series High Performance Universal Inverter User’s Manual Function 0xT7 read and write multiple parameters PDU Part Contents Data Length (Byte) Range Request (Response): Function code 0xT7 The start address of reading register 0x0000~0xFFFF The number of reading register...
Page 150
E5 Series High Performance Universal Inverter User’s Manual Control word registers: 0x8000 ~ 0x800D Register Name of Parameters Register Name of Parameters 0x8000 0x8007 Control command word AOT output host computer percentage 0x800T Open loop digital frequency reference 0x8008...
Page 151
E5 Series High Performance Universal Inverter User’s Manual Control command word (0x8000) description Meaning Meaning 0: Stop command 0: Jog running is inactive T: Run command T: Jog running is active 0: Run forward 0: Emergency stop is inactive T: Run reverse...
Page 152
E5 Series High Performance Universal Inverter User’s Manual Register for parameter attributes Register Read (R) and Meaning Range address Write (W) 0xF080 Relative address of the parameter See Appendix Table−T 0xF08T Current value 0 ~ 65535 0xF08T Upper limit...
Page 153
E5 Series High Performance Universal Inverter User’s Manual 8. Communication Bus Topology Bus topology of master and slave Appendix Figure3 Bus topology of master and slave Bus topology of master and slaves With shielded twisted pair GND 485+ 485-...
E5 Series High Performance Universal Inverter User’s Manual Appendix B E5 Series Hardware Non-standard List T. E5 Series Hardware Non-standard List Refer to the “T.T Product Model Description” in Chapter T Hardware Function non-standard Replace operation panel type(V6−DP0T or V6−DP0T), if 7.5kW and below power class needed V6−DP0T or TTkW and above power class needed V6−DP0T, this suffix should be added to...
E5 Series High Performance Universal Inverter User’s Manual Appendix C EX−DT01 Digital Terminal Extension Card T. EX−DT0T Description EX−DT0T digital terminal extension card is used for extension of digital input and relay output terminal. EX−DT0T has four digital input terminals and three relay output terminals.
Page 156
E5 Series High Performance Universal Inverter User’s Manual 3. Wiring mode Apply EX−DT0T internal +T4V power supply, Apply external power supply, wiring in NPN sink wiring in NPN sink current wiring mode current wiring mode External controller 20~T8V +3.3V...
Page 157
English version: E5−20190618−1.0 (BOM: 37110286printed for the first time This document is subject to change without notice. All rights reserved. Any unauthorized reproduction or copy is forbidden. Shenzhen V&T Technologies Co., Ltd. Address: 11f. Kenuo building, Kenuo Industrial Park, No.7, Tongguan Avenue, Guangming District, Shenzhen City, China Postcode: 518107 Market Tel: +86 755 29043763...