frequency. When standard AC motor is used, it corresponds to the motor rated voltage. Refer to motor
nameplate.
The frequency high limit f
of the motor set according to the production process requirement by the user during the use.
The basic operating frequency f
voltage of the inverter. When standard AC motor is used, it corresponds to the rated frequency of the
motor. Refer to the motor nameplate.
P0.16
Effect of the torque boost function: when the inverter operation at low−frequency, increase the output
voltage, and offset the stator voltage drop to product enough torque, so as to ensure the normal
operation of the motor.
Note:
The torque boost amplitude should be set according to the load situation. Excessive boost will
cause large current impact during the startup process.
When P0.16 is set to 0.0, and P4.00 is set to 0 (linear V/F curve), the automatic torque boost is
enabled; when P4.00 is set to a non−zero value, the automatic torque boost is disabled.

6.2 Main and Auxiliary Reference Parameter (Group P1)

P1.00
P1.01
In process open loop control mode (P0.03=0), the main reference value f
reference value f
, and it results in process open loop combination frequency reference f
a
E5−H High Performance Universal Inverter
and frequency low limit f
H
is the minimum frequency corresponding to the maximum output
b
Output voltage
Output voltage
Figure 6−2 Characteristic parameter definition
Torque boost
Open loop auxiliary reference mode
Open loop reference main and auxiliary relation
calculation
Figure 6−3 Open loop main and auxiliary reference combination
Chapter 6 Parameter Description
User Manual
are the maximum and minimum operating frequency
L
Output frequency
Output frequency
0.0~30.0 %(0.0%)
0~2(0)
0~5(0)
will be added with an auxiliary
m
.
com
57