V&T E5-H Series User Manual page 46

High performance universal inverter
Table of Contents

Advertisement

Function
code
Function code name
number
Open loop digital
P0.05
frequency reference
Running command
P0.06
issuing mode
Running direction
P0.07
command
P0.08
Acceleration time 0
P0.09
Deceleration time 0
P0.10
S−curve time
Maximum output
P0.11
frequency
Maximum output
P0.12
voltage
P0.13
Frequency high limit
P0.14
Frequency low limit
Basic operating
P0.15
frequency
P0.16
Torque boost
Open loop auxiliary
P1.00
reference mode
Open loop reference
P1.01
main and auxiliary
relation calculation
Analog feedback close
P1.02
loop control main
reference mode
Analog feedback close
P1.03
loop control auxiliary
reference mode
Analog feedback close
loop control reference
P1.04
main and auxiliary
calculation
Analog feedback close
P1.05
loop control main
feedback mode
Analog feedback close
P1.06
loop control auxiliary
feedback mode
Analog feedback close
loop control feedback
P1.07
main and auxiliary
calculation
Key − lock function
P2.00
selection
E5−H High Performance Universal Inverter
Factory
Setting range
setting
50.00
0.00 ~ 300.00
0
0 ~ 2
0
0 ~ 1
6.0
0.1 ~ 3600.0
20.0
0.0
0.0 ~ 3600.0
50.00
0.01 ~ 300.00
380
1 ~ 480
50.00
0.00 ~ 300.00
0.00
0.00 ~ 300.00
50.00
0.00 ~ 300.00
0.0
0.0 ~ 30.0
Group P1
Main and Auxiliary Reference Parameter
0
0 ~ 2
0
0 ~ 5
0
0 ~ 2
0
0 ~ 2
0
0 ~ 5
1
1 ~ 2
0
0 ~ 2
0
0 ~ 5
Group P2
Key and Display Parameters
0
0 ~ 3
Chapter 5 List of Parameters
User Manual
Unit
Property
Function code selection
High / low frequency limit (P0.13 ~
Hz
P0.14)
0: Operation panel;
/
1: Terminal;
2: Host computer
/
0: Run forward; 1: Run reverse
15kW and below
s
18.5kW and above
s
0.0 ~ 3600.0s
Hz
×
High frequency limit P0.13 ~ 300.00Hz
V
×
1 ~ 480V
Lower frequency limit P0.14 ~
Hz
×
Maximum output frequency P0.11
Hz
×
0.00Hz ~ High frequency limit P0.13
0.00Hz ~ Maximum output frequency
Hz
×
P0.11
0.0: Auto torque boost;
%
×
0.1% ~ 30.0%
/
×
0: None 1: AI1; 2: AI2
0: Main + Auxiliary;
1: Main − Auxiliary;
2: Auxiliary−50%;
/
×
3: Main + Auxiliary−50%;
4: Take the maximum value;
5: Take the minimum value
0: Digital voltage reference P8.00;
/
×
1: AI1; 2: AI2
0: None;
/
×
1: AI1; 2: AI2
0: Main + Auxiliary;
1: Main − Auxiliary;
2: Auxiliary−50%;
/
×
3: Main + Auxiliary−50%;
4: Take the maximum value;
5: Take the minimum value
/
×
1: AI1; 2: AI2
0: None;
/
×
1: AI1; 2: AI2
0: Main + Auxiliary;
1: Main − Auxiliary;
2: Auxiliary−50%;
/
×
3: Main + Auxiliary−50%;
4: Take the maximum value;
5: Take the minimum value
0: No locking;
1: Locking all keys;
/
2: Locking all keys except MULTI key;
3: Locking all keys except RUN and
STOP/RST keys
User
setting
0.1 ~
3600.0s