Figure 6−26 AO1 Characteristics Curve−Kx+b
Note: When the analog output gain is set to negative value and the bias is also negative, the AO output
will be limited to 0V automatically.
P7.11
This function code determines Y1 and relay output signal type selection (level or pulse).
Note: The life of relay is about 10 million times, frequent open and close will be shortened use of time.
P7.12
P7.13
P7.16
P7.17
Terminal delay time on the level or the pulse output signals are enabled, terminal pulse width defines the
effective holdup time of pulse signal.
Figure 6−28 in the Yi on behalf of Y1, relay terminal, in order to keep the waveform consistent before
delay and after delay, need to ensure that the output signal width> Yi terminal delay setting, if the output
signal width <Yi terminal delay setting, the signal will be ignored.
82
E5−H High Performance Universal Inverter
Output signal type
Display of operation panel
Unit place
Y1 terminal:
Tens place
Reserved
Hundreds place
Relay terminal: 0: Level signal; 1:Pulse signal
Y1 terminal delay time
Y1 terminal pulse width
Relay terminal delay time
Relay terminal pulse width
Chapter 6 Parameter Description
User Manual
Figure 6−27 AO1 Characteristics Curve−Kx+b
0:Level signal; 1:Pulse signal
000 ~ 101(000)
0.0~999.9s (0.0s)
0.0~999.9s (0.0s)
0.0~999.9s (0.0s)
0.0~999.9s (0.0s)