The bits for the control command word (0x8000) of the inverter are defined as follows:
Bit
0: Stop
0
command enable
1
0: Run forward
0: Reset
2
command disable
Note: Bits 4 ~ 13 are reserved.
The bits for the status word1 (0x810B) of the inverter are defined as follows:
Bit
0
0: Inverter stop
3
0: Run forward
4
0: Button unlocked
Note: Bits 1, 2 and 7 are reserved.
The bits for the status word 4(0x810E) of the inverter are defined as follows:
Bi
t
0
0: Non−jog running
0: Non−close loop
1
operation
0: Non−open loop multi−section frequency
operation
2
1: open loop multi−section frequency
operation
0: Non−close loop multi−section frequency
operation
3
1: Close loop multi−section frequency
operation
0: Non−common
4
operation
Note: Bits 8 ~ 13 are reserved.
Special register for input password authentication
Sub function
code of PDU
0xF000
0xF001
0xF002
120
E5−H High Performance Universal Inverter
Meaning
1: Running
command enable
1: Run reverse
1: Reset
command enable
Meaning
1: Inverter running
1: Run reverse
1: Button locked
Meaning
1: Jog running
1: Close loop
operation
1: Common
operation
Inverter user password P0.00 authentication, and it will be closed automatically if no operation
is performed within five minutes.
PE.00 password authentication for the display and hidden areas of the specially authenticated
function codes of the inverter, and it will be closed automatically if no operation is performed
within five minutes.
A0.00 password authentication for the display and hidden attributes customized areas of the
function codes of the inverter, and it will be closed automatically if no operation is performed
within five minutes.
Appendix A Modbus Communication Protocol
Bit
0: Jog command
3
disable
0: Emergency stop
14
disable
0: Coast to stop
15
disable
Bit
Running command issuing mode selection:
0: Operation panel reference,
5~6
1: Terminal reference,
2: host computer reference.
8 to 15
0: Normal; others: Failure code
Bit
0: Non−open loop
5
multi−section voltage
operation
6
0: Normal voltage
7
Reserved
14
0: Speed control
0:
without
15
control
Attached Table−4
Meaning
User Manual
Meaning
1: Jog command
enable
1: Emergency stop
enable
1: Coast to stop
enable
Meaning
Meaning
1: Open loop
multi−section voltage
operation
1: Under voltage
Reserved
1: Reserved
vector
Reserved