V&T E5-H Series User Manual page 86

High performance universal inverter
Table of Contents

Advertisement

Function setup
20
Output X2
Zero current detection arrival (relative
22
to motor)
24~31
Reserved
33~47
Reserved
0: Signal indicating that the inverter is running (RUN)
The signal is enabled when the inverter is running.
1: Frequency arrival signal (FAR)
When the deviation between the output frequency and the setup frequency of the inverter is in the setup
range of the frequency arrival detection width, the signal is enabled. Refer to P7.19 for details.
2: Frequency level detection signal (FDT1)
When the output frequency is higher than FDT1 level high limit, the signal is enabled. When the output
frequency is less than FDT1 level low limit, the signal is disabled. Refer to P7.20 ~ P7.21 for details.
3: Frequency level detection signal (FDT2)
When the output frequency is higher than FDT2 level high limit, the signal is enabled. When the output
frequency is less than FDT2 level low limit, the signal is disabled. Refer to P7.22 ~ P7.23 for details.
4: Pre−warning signal indicating inverter overload or motor overload (OL)
When the output current is higher than the overload pre−warning detection level and the retention time is
higher than the overload pre−warning detection time, the signal is enabled. When the current is lower
than the detection level, the signal is disabled. Refer to PA13 ~ PA.15 for details.
5: Stop and lock due to under voltage (LU)
When the inverter bus voltage is lower than the under voltage action value, the signal is enabled.
6: Stop due to external failure(EXT)
When the inverter is in the protection status due to failure of peripherals ("E.oUt" appears on the
operation panel), the signal is enabled.
7: Frequency high limit (FHL)
When the inverter output frequency reaches setup frequency high limit, the signal is enabled.
8: Frequency low limit (FLL)
When the inverter output frequency reaches setup frequency low limit, the signal is enabled.
9: Inverter is running at zero speed.
When the inverter output frequency is 0, the single is enabled.
10: Preset counting value action
11: Counting value arrival action
When the counting value of inverter input terminal complies with action, the signal is enabled, Refer to
P5.12 and P5.13 for details.
13: Inverter ready for operation (RDY)
When the auto−test of the inverter is normal after power on and the inverter operation disable function is
disabled or disable, the signal is enabled.
14: Inverter fault
When the inverter is in the stop status due to failure, the signal is enabled.
E5−H High Performance Universal Inverter
Meaning
Chapter 6 Parameter Description
User Manual
Function setup
21
Reserved
23
Stop command indication
32
Sleeping state indication
Meaning
79

Advertisement

Table of Contents
loading

Table of Contents