V&T E5-H Series User Manual page 106

High performance universal inverter
Table of Contents

Advertisement

0: No action after power resumes normal.
1: Action after power resumes normal.
The function supports automatic operation of the inverter when the power to the inverter resumes normal
after power failure. Be careful in using this function.
When restart after power failure is selected, the inverter will operate automatically after power on under
any operating command reference mode, such as operation panel operating command reference,
terminal operating command reference or host computer operating command reference.
When restart after power failure is selected, if P0.06=1 and the running terninal is enabled when power
on, the inverter will start running after the power resumes.
Note: To ensure this function is enabled under terminal operating command reference mode, please do
not change the status of operating command terminal during shutdown.
Pb.17
Pb.18
When the inverter operates, the function can response the setting of reference channel for other
frequencies after using the pre−set frequency as the setting frequency and keeping the time as pre−set
frequency operating time Pb.18.
Pb.19
Pb.20
This function supports sleeping function and energy saving operation. After running, the inverter will start
when the setting frequency≥Pb.19. During operation, the inverter operates at zero frequency when the
setting frequency≤Pb.20. Proper setting of limit value of zero operation can avoid the inverter starting
and stopping frequently. If the inverter is often used for work situations such as air condition and fan,
change the analog signal of temperature sensor to setting frequency to control automatic starting or
stopping of inverter.
Pb.21
E5−H High Performance Universal Inverter
Pre-set frequency
Pre-set frequency operating time
High limit of zero frequency operation
Low limit of zero frequency operation
Figure 6−36 High and low limit of zero frequency operation
Fan and pump control mode selection
Chapter 6 Parameter Description
User Manual
0.00~300.00 Hz(0.00Hz)
0.0~3600.0 s(0.0s)
0.00~300.00 Hz(0.00Hz)
0.00~300.00 Hz(0.00Hz)
0~3(0)
99

Advertisement

Table of Contents
loading

Table of Contents