V&T E5-H Series User Manual page 77

High performance universal inverter
Table of Contents

Advertisement

executed in the running status and the running command will not be executed in the jog status.
4: Three−line running control
It is only enabled when the running command is issued via terminal ((P0.06=1). Refer to P5.11 for the
instructions about its application.
5: Reserved
6: Multi−section digital voltage terminal 1
7: Multi−section digital voltage terminal 2
8: Multi−section digital voltage terminal 3
Refer to P4.15 ~ P4.21 for the instructions about its application.
9: Multi− section frequency terminal 1
10: Multi− section frequency terminal 2
11: Multi− section frequency terminal 3
12: Multi− section frequency terminal 4
Refer to P4.22 ~ P4.36 for the instructions about its application.
13: Acceleration/deceleration time terminal 1
14: Acceleration/deceleration time terminal 2
Refer to the table below for the instructions about its application.
Acceleration/deceleration
terminal 2
OFF
OFF
ON
ON
15: Digital regulating frequency reset
It is used to reset the change values of the setup frequency regulated by the operation panel
terminal UP/DN. When this terminal is enabled, the operation panel
disabled.
16: Frequency increase command
17: Frequency decrease command
The two terminals are used to modify the setup frequency with UP/DN key.
18: Acceleration/deceleration disable command
If this terminal is enabled, the running frequency will remain unchanged unless stop command is
executed.
19: External failure input
When this terminal is enabled, inverter will stop running and display "E.oUt" failure.
20: Terminal failure reset input
This terminal is used to reset failure, which can also be done with the STOP/RST key on the operation
panel and the host computer command.
70
E5−H High Performance Universal Inverter
Acceleration/deceleration
terminal 1
OFF
ON
OFF
ON
Chapter 6 Parameter Description
User Manual
Acceleration/deceleration time
selection
Acceleration/deceleration time 0
(P0.08 and P0.09)
Acceleration/deceleration time 1
(P4.09 and P4.10)
Acceleration/deceleration time 2
(P4.11 and P4.12)
Acceleration/deceleration time 3
(P4.13and P4.14)
/
and terminal
∧ ∨
/
and
∧ ∨
UP/DN are