V&T E5-H Series User Manual page 88

High performance universal inverter
Table of Contents

Advertisement

calculate by motor rotate speed.
2. The "Host computer percentage" is the frequency or pressure reference.
P7.05
P7.06
P7.07
P7.08
P7.09
This function code can be used to adjust the analog outputs defined in the above table. The adjusted
analog value is the actual output of AO terminal.
P7.09 is used to determine the positive and negative polarities of the gain or bias.
Since function codes P7.05 ~ P7.09 are different from other function codes, adjustment will affect the AO
output timely, that is, by debugging the parameters P7.05-P7.09, you will get the analog output of A01
and A02.
Both AO1 and AO2 have the same calibration way. Take AO1 as an example:
Set P7.05 to 100.0% and P7.06 to 20.0%,namely, K=1 and b=2V, and the AO1 characteristics curve is as
shown in Figure 6−24 and Figure 6−25.
Figure 6−24 AO1 Characteristics Curve Kx+b
Set P7.05 to 100.0% and P7.06 to 120.0%, namely, K=1 and b=12V, and the AO1 characteristics curve is
as shown in Figure 6−26.
Set P7.05 to 100.0% and P7.06 to 80.0%, namely, K=1 and b=8V, and the AO1 characteristics curve is
as shown in Figure 6−27.
E5−H High Performance Universal Inverter
AO1 gain
AO1 bias
AO2 gain
AO2 bias
Selection of positive and negative gain and bias
Display of operation panel
Unit place
AO1 gain 0: Positive; 1: Negative
Tens place
AO1 bias 0: Positive; 1: Negative
Hundreds
AO2 gain 0: Positive; 1: Negative
place
Thousands
AO2 bias 0: Positive; 1: Negative
place
Chapter 6 Parameter Description
User Manual
0.0 ~ 200.0 %(100.0%)
0.0 ~ 200.0 %(100.0%)
Figure 6−25 AO1 Characteristics Curve Kx−b
0.0 ~ 200.0 %(0.0%)
0.0 ~ 200.0 %(0.0%)
0~1111(0000)
81

Advertisement

Table of Contents
loading

Table of Contents