Note: The signal can be identified only when the X1/X2 signal pulse width larger than X1/X2 terminal
delay time. See Figure 6−13, t
P5.11
P5.11 is used to set the mode of controlling the startup and stop of the inverter with FWD and REV
terminals when the running command is issued via terminal.
0: Two line 1;
FWD
FWD
REV
REV
Inverter
Inverter
COM
COM
Figure 6−14 Two−line running mode 1
1: Two line 2;
Inverter
Inverter
Figure 6−15 Two−line running mode 2
E5−H High Performance Universal Inverter
Figure 6−13 X1/X2 terminal delay
can be identified and t
w1
Startup/stop mode Selection
K1
K1
K2
K2
Chapter 6 Parameter Description
User Manual
will be ignored.
w2
FWD
REV
0
0
0
1
1
0
1
1
FWD
REV
0
0
0
1
1
0
1
1
0 ~ 3(0)
Start−up and
stop
command
Stop
Run reverse
Run forward
Stop
Start−up and
Stop
Stop
Stop
Run forward
Run reverse