3.8 Functions of Control Circuit Terminals

Terminal
Type
symbol
Operation
CN7
panel RS485
+24V
PLC
Digital input
X1~X4
COM
Digital output
COM
+10V
Analog input
AI1
AI2
GND
AO1
Analog
output
AO2
GND
Relay output
RA/RB/RC
Note:
*: If you use computer to control the inverter, you can control 32 piece paralleled inverters, but you can't
use one operation panel of the inverter to control 32 piece paralleled inverters.
﹡ If the user connects adjustable potentiometer between +10V and GND, the resistance of the
potentiometer shall be no less than 5kΩ,
E5−H High Performance Universal Inverter
Terminal function
description
RS485 port of operation panel
+24V
Common end of
multi−functional input terminal Short circuited with +24V upon delivery
Multi−functional input
terminals 1 ~ 4
+24V grounding
Y1
Open collector output
Open collector output
common end
Analog input reference
voltage
Analog input channel 1
Analog input channel 2
Analog grounding
Analog output 1
Analog output 2
Analog grounding
Relay output
Chapter 3 Wiring of Inverter
User Manual
Technical specification
Rate: 38400bps
Up to 32 sets of equipment can be paralleled*. Relay
shall be used if the number exceeds 32.
The maximum distance is 15m for the communication
connection of operation panel
(adopt standard twisted non−shielded network cable)
24V±10%, internal isolated with GND
Maximum load: 200mA, with overload and short circuit
protection
Input specification: 24VDC,5mA
Frequency range: 0~200Hz
Voltage range: 24V±20%
Internal isolated with GND
Voltage range: 24V±20%, maximum input current: 50mA
Internal isolated with GND
10V ±3%, internal isolated with COM
Maximum output current: 10mA, with short circuit and
overload protection
0~20mA: Input impedance 500Ω, maximum input
current: 30mA
0~10V: Input impedance 20kΩ, maximum input
voltage : 15V
Resolution: 12 bits (0.025%)
0~20mA or 0~10V analog input can be selected
through jumper
Same as AI1
Internal isolated with COM
0~20mA: allowable output impedance 200~500Ω
0~10V: allowable output impedance ≥10kΩ
Output precision: 2%, resolution: 10 bits (0.1%)
with short circuit protection function
0~20mA or 0~10V analog output can be selected
through jumper
Same as AO1
Internal isolated with COM
RA−RB: Normally closed
RA−RC: Normally open
Contact capacity: 250VAC/1A, 30VDC/1A