Abnormal
code
0x01
0x02
0x03
0x04
0x05
0x06
4. Function Interpretation
Function 0x03 reads parameters and status words of multiple function code parameters of the inverter.
PDU Part Contents
Request:
Function code
Initial
address
register
Number of registers
Response:
Function code
Read bytes
Read contents
Function 0x06(0x41) rewrites single function code or control parameter of the inverter and save it upon
power failure (not save).
PDU Part Contents
Request:
Function code
Register address
Register data
Response:
Function code
Register address
Register data
Note: if change function code frequently, such as change setting frequency repeat, suggest use 0x41
command is better than 0x06, prevent from damage inner EEPROM.
116
E5−H High Performance Universal Inverter
Definition
Illegal function code
Illegal data address
Illegal data, data beyond
high/low limits
Slave operation failure, the
data is within the range of
high/low limits, but it is
disabled.
Order valid, in process, mainly
occurs upon storing data into
EEPROM
Slave busy, mainly occurs
upon storing data into
EEPROM
Data Length (Byte)
1
of
2
2
1
1
2*Number of registers
Data Length (Byte)
1
2
2
1
2
2
Appendix A Modbus Communication Protocol
User Manual
Abnormal
code
Frame error: frame length error,
0x20
check error
0x21
Parameters are unchangeable.
Unchangeable upon operation
0x22
of parameters
Password protected for
0x23
parameters
Non− host computer equipment
0x24
control, invalid host computer
command
0x0000 ~ 0xFFFF
0x0001 ~ 0x0010
2*Number of registers
0x0000 ~ 0xFFFF
0x0000 ~ 0xFFFF
0x0000~ 0xFFFF
0x0000 ~ 0xFFFF
Definition
Range
0x03
0x03
Range
0x06(0x41)
0x06(0x41)